Plan Review Notes
Plan Review Notes For Permit 07030437
Permit Number 07030437
Review Stop M
Sequence Number 1
Notes
Date Text
2007-04-03 11:16:16*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM600B-04R (OR
 600A-04R), SEE 2004 FBC 13-600.3.B (12-8-06 REVISION).
  
 2)ENERGY CALCULATIONS NEED TO BE SIGNED BY
 OWNER/AGENT ALSO, PER 2004 FBC 13-600.3.ABC.2.
  
 3) PLEASE SUBMITCOOLING LOAD CALCULATIONS, PER 2004
 FBC 13-607.1.ABC.1 .
  
 4) THE A/C EQUIPMENT SCHEDULE ON THE MECHANICAL PLANS
 PAGE 4 OF 4 NEEDS TO SHOW THE SENSIBLE BTU'S. ALSO.
  
 5) MOST OF THE SUPPLY AIR DUCTS ARE NOT SIZED, SEE THE
 YELLOW HIGH LIGHTS ON THE MECHANICAL PLANS, PLEASE
 CORRECT.
  
 6) THE RETURN AIR TRANSFER DUCTS FROM BEDROOM #1 TO
 BEDROOM #2 AND FROM BEDROOM #2 TO BEDROOM #3 NEEDS TO
 BE SIZED.
  
 7) THE 9" RETURN AIR TRANSFER DUCT FROM BEDROOM #3 TO
 THE HALLWAY MAY BE TO SMALL AS IT IS RETURNING AIR FROM
 THE THREE BEDROOMS, SEE 2004 FBC/R M1602.4.
  
 ** 2004 FBC/R M1602.4 BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY INCREASING THE
 RETURN TRANSFER ONE AND ONE HALF TIMES THE CROSS
 SECTIONAL AREA (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING AND THE DOOR
 HAVING AT LEAST AN UNRESTRICTED 1 INCHUNDERCUT TO
 ACHIEVE PROPER RETURN AIR BALANCE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.