 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PLEASE LOCATE ALL SERVICE EQUIPMENT ON THE PLAN,
 METER ENCLOSURE, DISCONNECTS AND PANELS, SO THAT
 COMPLIANCE WITH ARTICLES 225 AND 230 CAN BE REVIEWED.
  
 2} CIRCUIT #19 DOES NOT COMPLY WITH210.52(B)(1) FOR
 KITCHEN (SMALL APPLIANCE) CIRCUITS.
  
 3} IF CIRCUIT #27 IS MEANT FOR THE DINNING ROOM
 RECEPTALES, IT ALSO VIOLATES 210.52(B)(1). SEPERATE THE
 LIGHTING FROM THE RECEPTACLES IN THIS AREA. SEE 408.4,
 2005 NEC FOR CLARIFICATION.
  
 4} INDICATE IF THE PROPOSED SERVICE IS OVERHEAD OR
 UNDERGROUND. 215.5.
  