Plan Review Notes For Permit 07030373 |
Permit Number |
07030373 |
|
Review Stop |
P |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-04-09 09:37:21 | ****************PROVISO**************** | | SHEET 2: P.O.C. TO COOLING TOWER REFILL SHALL BE | | PROTECTED WITH A REDUCED PRESSURE PRINCIBLE BACKFLOW | | PREVENTER PER FBC-2004 PLUMBING, SECTION 608. |
|