Plan Review Notes For Permit 07030345 |
Permit Number |
07030345 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-03-12 15:41:47 | *** DENIED *** | | 1) PLEASE SHOW ON PLANS, SUPPLY AIR GRILLS AS SQUARES | | OR RECTANGLES WITH AN X IN THEM, AND SHOW RETURN GRILLS | | WITH AN / IN THEM. | | | | 2) PLEASE SHOW ON PLANS THE MAIN RETURN AIR GRILL AND | | SIZE. | | | | 3) PLEASE PROVIDE RETURN AIR FOR THE FAMILY ROOM, SEE | | 2004 FBC/R M1602.4. | | | | 4) PLEASE SHOW THE CFM'S AT ALL SUPPLY AIR GRILLS. | | | | 5)ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND | | ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND | | SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER | | FBC 104.2.1 . | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. | | | | | | |
|