Plan Review Notes For Permit 07030341 |
Permit Number |
07030341 |
|
Review Stop |
G |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2007-07-25 08:34:54 | REVISION: CHANGE TYPE OF WATER HEATER AND LOCATION. | | | | ****************PROVISO**************** | | A} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR | | VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED | | IMMEDIATELY AHEAD OF EACH MP REGULATOR. | | | | IF DRYER ROOM IS A CONFINED SPACE, OPEN- | | INGS REQUIRED PER SECTION 304.5 OR | | SECTION 304.6 SHALL BE INSTALLED. | | MINIMUM 1,100 CUBIC FEET REQUIRED. | | | | REVIEW BY MIKE PERSON | | PLUMBING PLANS EXAMINER | | (561) 805-6730 | | FAX (561) 805-6731 | | E-MAIL= [email protected] | | |
|