2007-07-25 08:34:54REVISION: CHANGE TYPE OF WATER HEATER AND LOCATION.
  
 ****************PROVISO****************
 A} PER FBC-2004 FUEL GAS, SECTION 409.4 MP REGULATOR
 VALVES: A LISTED SHUTOFF VALVE SHALL BE INSTALLED
 IMMEDIATELY AHEAD OF EACH MP REGULATOR.
  
 IF DRYER ROOM IS A CONFINED SPACE, OPEN-
 INGS REQUIRED PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  