Date |
Text |
2007-06-04 11:00:12 | DENIED REVISION |
| REFERENCE: |
| ** FBC-2004 FUEL GAS. |
| ** THE CITY OF WEST PALM BEACH GAS PERMIT APPLICATION |
| REQUIREMENTS. |
| ** FBC-2004 CHAPTER 1, THE CITY OF |
| WEST PALM BEACH AMENDMENTS. |
| ** FLORIDA ADMINISTRATIVE CODE. |
| ** FLORIDA STATUTES. |
| |
| THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR |
| GAS PLAN REVIEW ON THE REVISION TO MEET CODE |
| COMPLIANCE: |
| NOTE: THE PLAN REVISION FORM ADDRESS OF JOB WAS |
| INCORRECTLY INDICATED AS THE ADDRESS OF CONTRACTOR, |
| PLEASE SEE RED LINE CORRECTIONS OF THIS AND PLEASE |
| SUBMIT THE CORRECT ADDRESS OF JOB ON FUTURE REVISIONS. |
| ALSO NOTE THAT REVISION FEES ARE OWED FOR THIS REVISION |
| OF $60.00 AND REVISION FEES WILL BE REQUIRED FOR THE |
| CORRECTED REVISION SUBMITTAL. |
| |
| 1. SUBMIT AN ISOMETRIC DRAWING THAT |
| CLEARLY SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. |
| NOTE: THE SUBMITTED REVISION IS NOT INDICATING ALL |
| CORRESPONING LENGTHS ON ALL CUT SECTIONS OF PIPE TO |
| VERIFY THE NEW INDICATED LONGEST RUN OF 75'. PLEASE |
| CLEARLY INDICATE THE GAS METER ON THE NEXT RESUBMITTED |
| REVISION. PLEASE CORRECT. |
| |
| 2. SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED. |
| NOTE: THE SUBMITTED REVISION IS NOT INDICATING ALL |
| PIPING MATERIALS BEING USED ON ALL CUT SECTIONS. |
| |
| 3. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| NOTE: THIS GOES ALONG WITH COMMENT NUMBER ONE. |
| |
| ********IMPORTANT INFORMATION******** |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. |
| NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |
| REVIEW BY MIKE PERSON |
| PLUMBING PLANS REVIEWER |
| (561) 805-6730 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |
| UNDER SUPERVISION OF K.STEVENS |
| (561) 805-6721 |