2007-04-17 13:57:07 | ****************PROVISO**************** | | PER FBC-2004 FUEL GAS, SECTION 409.4: A LISTED SHUTOFF | | VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF EACH MP | | REGULATOR. | | | | IF DRYER ROOM IS A CONFINED SPACE, OPENINGSREQUIRED | | PER SECTION 304.5 OR | | SECTION 304.6 SHALL BE INSTALLED. | | MINIMUM 1,100 CUBIC FEET REQUIRED. | | | | IF WATER HEATER ROOM IS A CONFINED | | SPACE, OPENINGS REQUIRED PER SECTION | | 304.5 OR SECTION 304.6 SHALL BE | | INSTALLED. | | MINIMUM 5,000 CUBIC FEET REQUIRED. |
|