Plan Review Notes
Plan Review Notes For Permit 07030341
Permit Number 07030341
Review Stop G
Sequence Number 2
Notes
Date Text
2007-04-17 13:57:07****************PROVISO****************
 PER FBC-2004 FUEL GAS, SECTION 409.4: A LISTED SHUTOFF
 VALVE SHALL BE INSTALLED IMMEDIATELY AHEAD OF EACH MP
 REGULATOR.
  
 IF DRYER ROOM IS A CONFINED SPACE, OPENINGSREQUIRED
 PER SECTION 304.5 OR
 SECTION 304.6 SHALL BE INSTALLED.
 MINIMUM 1,100 CUBIC FEET REQUIRED.
  
 IF WATER HEATER ROOM IS A CONFINED
 SPACE, OPENINGS REQUIRED PER SECTION
 304.5 OR SECTION 304.6 SHALL BE
 INSTALLED.
 MINIMUM 5,000 CUBIC FEET REQUIRED.