2007-05-08 13:34:07****************PROVISO****************
 A} PER FBC-2004 FUEL GAS SECTION 408.4 A SEDIMENT
 TRAP SHALL BE INSTALLED DOWNSTREAM OF THE EQUIPMENT
 SHUTOFF VALVE AS CLOSE TO THE INLET OF THE EQUIPMENT AS
 PRACTICAL.
  
 B} PER FBC-2004 FUEL GAS, SECTION 404.13.3AN
 INSULATED COPPER TRACER WIRE SHALL BE INSTALLED
 ADJACENT TO UNDERGROUND NONMETALLIC GAS PIPING. THE
 TRACER WIRE SIZE SHALL NOT BE LESS THAN 18 AWG AND THE
 INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL.
  