2007-03-12 11:08:27 | |
| |
| DENIED/INCOMPLETE INFORMATION |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW. |
| |
| 1} INDICATE THE CONDUCTOR AND CONDUIT SIZE AND TYPE |
| FEEDING THE "NEW METER & SWITCH", SO IT CAN BE |
| DETERMINED IF COMPLIANCE WITH 310.16 AND 250.122 ARE |
| MET. |
| |
| 2} INDICATE THE CONDUIT TYPE FROM THE DISCONNECT AT THE |
| METER TO THE NEW GUTTER. 106.3.5.1.2 FBC. FROM THE |
| GUTTER TO THE DISCONNECTS, SEE 430.28, 2005 NEC. |
| |
| 3} INDICATE THE CONDUIT AND CONDUCTOR SIZES TOALL |
| EQUIPMENT, ON THE RISER AND THE PLAN. INSTALL AN |
| EQUIPMENT GROUND IF REQUIRED. |
| |
| 4} VERIFY THE PANEL DESIGNATION ( HP1) FOR THE ROOF |
| RECEPTACLEREQUIRED BY 210.63,THE NUMBER OF |
| CONDUCTORS AND CONDUIT SIZE AND TYPE. |
| |
| 5} PROVIDE A LEGEND FORTHE DESIGNATIONS USED FOR THE |
| DISCONNECTS ON THE PLAN. IG: IT APPEARS THE DISCONNECT |
| FOR THE 15 HP PUMPS IS A 60 AMP, FUSED AT 40 WP?AND THE |
| RATED AMPERAGE IS 48.3. THE 7.5 HP. FAN AT 75 W. THE |
| PLAN BELOW THE RISER HAS THAT SAME FAN ON A 40 AMP FUSE |
| OR BREAKER. PLEASE CORRELATE. |
| |
| 6}INDICATE WHETHER THIS IS NEW OR REPLACEMENT |
| EQUIPMENT. IF IT IS NEW OR LARGER REPLACEMENT |
| EQUIPMENT, WATTAGE WISE, A LOAD CALCULATION FOR THE |
| SERVICE MUST BE SUBMITTED. |
| |
| 7} THE ENGINEER OF RECORD SHALL INDICATE THE |
| CERTIFICATE OF AUTHORIZATIONNUMBER ALONG WITH OTHER |
| INFORMATION REQUIRED BY 61G15-23.002FLORIDA |
| ADMINISTRATIVE CODE. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |
| BILL TROBAUGH |
| ELECTRICAL PLANS EXAMINER |
| CITY OF WEST PALM BEACH |
| 561/805-6718 |
| [email protected] |