Plan Review Notes For Permit 07030281 |
Permit Number |
07030281 |
|
Review Stop |
B |
Sequence Number |
5 |
|
Notes |
Date |
Text |
2008-05-20 15:34:23 | REVISION COMMENTS FOR THE TRANSFORMER CHANGE OF | | LOCATION. | | | | | | ENGINEER OF RECORD FOR THE BASE BUILDING SHALL SUBMIT | | STRUCTURAL CALCULATIONS FOR REVIEW. | | PROVIDE COMPLETE INSTALLATION DETAIL INCLUDING ALL | | MATERIALS AND HARDWARE. | | EXPLAIN REFERENCE TO W21, THE 12TH FLOOR FRAMING PLAN | | CALLS FOR W24, 30, AND 36. | | ALL SUBMITTALS SHALL BE SIGNED AND SEALED. | | | | | | | | | | | | LUIS MARTINEZ | | 561-805-6710 |
|