2007-09-17 17:05:07REVIEW #:
 ACTION:
  
 FBC 2004 CODE FAMILY W/ 2005 AND 2006 SUPPLEMENTS
 FBC CH.1 AS AMENDED BY THE CITY OF WEST PALM BEACH
  
 THE FOLLOWING COMMENTS ARE NUMBERED TO CORRESPOND WITH
 PREVIOUS REVIEW COMMENTS AS WELL AS DESIGNER'S WRITTEN
 RESPONSES FOR THE PURPOSE OF CONTINUITY.
  
 PREVIOUS REVIEW COMMENTS HAVE BEEN ADEQUATELY
 ADDRESSED.
  
 PLEASE ADDRESS THE FOLLOWIN NEW COMMENTS UPON
 RESUBMITTAL:
  
 1. IF THIS JOB IS TO UTILIZE A RESIDENT INSPECTOR, AS
 INDICATED BY THE LETTER FROM DAN PETROCCHI WHICH WAS
 INCLUDED WITH REVIEW COMMENT RESPONSES, A MINIMUM OF
 THREE COPIES OF ALL PLANS, SPECS, SUBMITTALS AND
 DOCUMENTATION SHALL BE PROVIDED IN ACCORDANCE WITH THE
 CITY OF WEST PALM BEACH RESIDENT AND SPECIAL INSPECTOR
 GUIDELINES AND POLICIES.
  
 2. SERVER ROOM 1222, PG H-1.1 SHOWS TWO DUCTS ENTERING
 ROOM WITH FIRE DAMPERS AS OPENING PROTECTIVES. PG
 A03.12 SHOWS THE WALLS TO TIS ROOM AS TYPE "032S" WHICH
 IS NOT A RATED WALL ASSEMBLY ACCORDING TO THE PARTITION
 TYPES SHOWN ON A14.10. FIRE DAMPERS CAN ONLY BE
 INSTALLED IN ACCORDANCE WITH THEIR LISTING AS REQUIRED
 BY FBC,M 607.2 IF THEY ARE INSTALLED WITHIN FIRE-RATED
 CONSTRUCTION. PLEASE COORDINATE ARCHITECTURAL PLANS AND
 MECHANICAL PLANS.
  