Plan Review Notes
Plan Review Notes For Permit 07030281
Permit Number 07030281
Review Stop P
Sequence Number 1
Notes
Date Text
2007-03-31 13:32:36PAUL SCHMITZ
 [email protected] FBC 2004 PLUMBING
 CODE PLAN REVIEW
 FBC2004 FUEL GAS CODEPLAN REVIEW
 FBC 2004 CH 11, FL ACESSIBILITY CODE
 AMENDMENTS TO THE FLORIDA BUILDING CODE
  
 CHAPT.1, ADMINISTRATION, 2004 EDITION
  
  
 DENIED
  
 1) SHT P-0.1WATER HEATER DETAIL (2)
 ICE MACHINE, I/W NOT APPROVED TO FLOOR DRAIN. 802.1.1
 FOOD HANDLING.
 EQUIPMENT AND FIXTURES UTILIZED FOR THE STORAGE,
 PREPARATION AND HANDLING OF FOOD SHALL DISCHARGE
 THROUGH AN INDIRECT WASTE PIPE BY MEANS OF AN AIR GAP.
  
 2)SHT H-0.3 DETAIL(3)A/C CONDENSATE TO FLOOR DRAIN
 NOT APPROVED TO SANITARY SEWER.
 WWF, ART.III SEWERS AND SEWAGE DISPOSAL, SEC. 90-125.
 (B) (5) A/C CONDENSATE TOTO SANITARY SEWER.
  
 3)SHT P-1.1 SHOWS TWOADDED DRINKING FOUNTAINS,
 PLEASE CORROLATE WITH, SHT A03.12, RM 1286B, DOES NOT
 SHOW A DRINKING FOUNTAIN.
  
 4) SHTA03.12 SHOWS FOUR BREAK ROOMS #
 1282,1284,1205,1256A. TO COMPLY WITH SEC 11-4.24
 11-4.24 SINKS.
 11-4.24.1 GENERAL.
 SINKS REQUIRED TO BE ACCESSIBLE BY SECTION 11-4.1 SHALL
 COMPLY WITH SECTION 11-4.24.
 11-4.24.2 HEIGHT.
 SINKS SHALL BE MOUNTED WITH THE COUNTER OR RIM NO
 HIGHER THAN 34 INCHES (865 MM) ABOVE THE FINISH FLOOR.
 11-4.24.3 KNEE CLEARANCE.
 KNEE CLEARANCE THAT IS AT LEAST 27 INCHES (685 MM)
 HIGH, 30 INCHES (760 MM) WIDE, AND 19 INCHES (485 MM)
 DEEP SHALL BE PROVIDED UNDERNEATH SINKS.
 11-4.24.4 DEPTH.
 EACH SINK SHALL BE A MAXIMUM OF 6? INCHES (165 MM)
 DEEP.
 11-4.24.5 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 SHALL BE PROVIDED IN FRONT OF A SINK TO ALLOW FORWARD
 APPROACH. THE CLEAR FLOOR SPACE SHALL BE ON AN
 ACCESSIBLE ROUTE AND SHALL EXTEND A MAXIMUM OF 19
 INCHES (485 MM) UNDERNEATH THE SINK (SEE FIGURE 32).
 11-4.24.6 EXPOSED PIPES AND SURFACES.
 HOT WATER AND DRAIN PIPES EXPOSED UNDER SINKS SHALL BE
 INSULATED OR OTHERWISE CONFIGURED SO AS TO PROTECT
 AGAINST CONTACT. THERE SHALL BE NO SHARP OR ABRASIVE
 SURFACES UNDER SINKS.
 11-4.24.7 FAUCETS.
 FAUCETS SHALL COMPLY WITH SECTION 11-4.27.4.
 LEVER-OPERATED, PUSH-TYPE, TOUCH-TYPE, OR
 ELECTRONICALLY CONTROLLED MECHANISMS ARE ACCEPTABLE
 DESIGNS.
 11-4.25 STORAGE.
 11-4.25.1 GENERAL.
 FIXED STORAGE FACILITIES SUCH AS CABINETS, SHELVES,
 CLOSETS, AND DRAWERS REQUIRED TO BE ACCESSIBLE BY
 SECTION 11-4.1 SHALL COMPLY WITH SECTION 11-4.25.
 11-4.25.2 CLEAR FLOOR SPACE.
 A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES
 (760 MM BY 1219 MM) COMPLYING WITH SECTION 11-4.2.4
 THAT ALLOWS EITHER A FORWARD OR PARALLEL APPROACH BY A
 PERSON USING A WHEELCHAIR SHALL BE PROVIDED AT
 ACCESSIBLE STORAGE FACILITIES.
 11-4.25.3 HEIGHT.
 ACCESSIBLE STORAGE SPACES SHALL BE WITHIN AT LEAST ONE
 OF THE REACH RANGES SPECIFIED IN SECTION 11-4.2.5 AND
 11-4.2.6 (SEE FIGURE 5 AND FIGURE 6). CLOTHES RODS OR
 SHELVES SHALL BE A MAXIMUM OF 54 INCHES (1370 MM) ABOVE
 THE FINISH FLOOR FOR A SIDE APPROACH. WHERE THE
 DISTANCE FROM THE WHEELCHAIR TO THE CLOTHES ROD OR
 SHELF EXCEEDS 10 INCHES (255 MM) (AS IN CLOSETS WITHOUT
 ACCESSIBLE DOORS) THE HEIGHT AND DEPTH TO THE ROD OR
 SHELF SHALL COMPLY WITH FIGURE 38(A) AND FIGURE 38(B).
 11-4.25.4 HARDWARE.
 HARDWARE FOR ACCESSIBLE STORAGE FACILITIES SHALL COMPLY
 WITH SECTION 11-4.27.4. TOUCH LATCHES AND U-SHAPED
 PULLS ARE ACCEPTABLE.
  
 5) PLAN REVIEW IN PROGRESS,