2007-04-04 16:54:42 | BUILDING PLAN REVIEW |
| PERMIT: 07030281 |
| ADD: 525 OKEECHOBEE BLVD/SUITE 1200 |
| CONT: CENTEX CONSTRUCTION |
| TEL: (954)214-9415 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| 1STREVIEW |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| THE COURT. |
| NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| NOT ACTUALLY |
| COMMENCED WITHIN 90 DAYS AFTER THE RECORDING THEREOF, |
| SUCH NOTICE IS |
| NULL & VOID. NOTE: 713.13(6)THE POSTING OF THE NOTICE |
| OF COMMENCEMENT |
| AT THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 3) SHEET A00-00 |
| 3A)ARCHITECTS JOVA/ DANIELS/ BUSBY ARCHITECTURAL FIRM |
| IS MISSING THEIR CERTIFICATE OF AUTHORIZATION: 481.219 |
| F.S.CERTIFICATE OF AUTHORIZATION.THE TITLE BLOCK |
| FOR ANY |
| SHEET BEARING THE NAME OF AN ARCHITECT PRACTICING UNDER |
| A FICTITIOUS NAME, A |
| CORPORATION, OR A PARTNERSHIP, OFFERING ARCHITECTURAL |
| SERVICES, SHALL INCLUDE |
| THE CERTIFICATE OF AUTHORIZATION NUMBER.ADD THE |
| NUMBER TO EACH SHEET. |
| THIS MAY BE ADDED BY HAND. |
| |
| 3B)ARCHITECTS SEAL IS A RUBBER SEAL NOT A EMBOSSED |
| RAISED SEAL.FL S S 481.221 |
| |
| 3C) PROJECT INFORMATION INDICATES THIS TO BE A 20 STORY |
| BUILDING PLEASE CORRECT. |
| |
| 3D) PLANS SUBMITTED AFTER DEC.8 2006 WILL BE REVIEWED |
| UNDER THE 2004 FBC BUILDING WITH THE 2006 AMENDMENTS |
| (REVISIONS). |
| |
| 3E) TITLE BLOCK:MISSING THE LOCATION OF THE |
| PROJECT. |
| 61G1-16.004 TITLE BLOCK. |
| A TITLE BLOCK MUST APPEAR ON ALL ARCHITECTURAL OR |
| INTERIOR DESIGN DRAWINGS AND SPECIFICATION |
| IDENTIFICATION SHEETS. THE TITLE BLOCK MUST, AT A |
| MINIMUM, CONTAIN THE FOLLOWING INFORMATION: |
| (1) FIRM NAME, ADDRESS, AND TELEPHONE NUMBER. |
| (2) FIRM LICENSE NUMBER. |
| (3) NAME OR IDENTIFICATION OF PROJECT. |
| (4) DATE PREPARED. |
| (5) A SPACE FOR THE SIGNATURE AND DATED SEAL. |
| (6) A SPACE FOR THE PRINTED NAME OF THE PERSON SEALING |
| THE DOCUMENT. |
| SPECIFIC AUTHORITY 481.2055 FS. LAW IMPLEMENTED |
| 481.203(6), 481.203(8), 481.2131(1), |
| 481.219(3),(4),(5), 481.221, 481.225(1)(E),(G), |
| 481.2251(1)(H) FS. HISTORY?NEW 9-7-00. |
| |
| 4) SHEET A03.12 THIS SHEET INDICATES VARIOUS BREAKROOMS |
| WITH SINKS, SEE CABINET ELEVATION SHEET A13.01: SINKS: |
| 11-4.24.2 SINKS, HEIGHT. SINKS SHALL |
| BE MOUNTED WITH THE COUNTER NO HIGHER |
| THAN 34" ABOVE THE FINISH FLOOR. |
| 11-4.24.3 KNEE CLEARANCE THAT IS AT |
| LEAST 27" HIGH 30" WIDE, AND 19" DEEP |
| SHALL BE PROVIDED UNDERNEATH SINKS. |
| 11-4.24.5 CLEAR FLOOR SPACE. |
| A CLEAR FLOOR SPACE AT LEAST 30 INCHES BY 48 INCHES |
| (760 MM BY 1219 MM) COMPLYING WITH |
| SECTION 11-4.2.4 SHALL BE PROVIDED IN FRONT OF A SINK |
| TO ALLOW FORWARD APPROACH. THE CLEAR |
| FLOOR SPACE SHALL BE ON AN ACCESSIBLE ROUTE AND SHALL |
| EXTEND A MAXIMUM OF 19 INCHES |
| (485 MM) UNDERNEATH THE SINK. |
| |
| 5)SHEET A14.01DETAILS 10& 11 BOTH INDICATE A WOOD |
| FINISH ON WALLS, UNDETERMINED WHAT IF THERE IS A BACKER |
| BOARD? |
| 803.4.2 SET-OUT CONSTRUCTION. |
| WHERE WALLS AND CEILINGS ARE REQUIRED TO BE OF |
| FIRE-RESISTANCE-RATED OR NONCOMBUSTIBLE CONSTRUCTION |
| AND WALLS ARE SET OUT OR CEILINGS ARE DROPPED DISTANCES |
| GREATER THAN SPECIFIED IN SECTION 803.4.1 , CLASS A |
| FINISH MATERIALS SHALL BE USED EXCEPT WHERE INTERIOR |
| FINISH MATERIALS ARE PROTECTED ON BOTH SIDES BY AN |
| AUTOMATIC SPRINKLER SYSTEM OR ATTACHED TO |
| NONCOMBUSTIBLE BACKING OR FURRING STRIPS INSTALLED AS |
| SPECIFIED IN SECTION 803.4.1 . THE HANGERS AND ASSEMBLY |
| MEMBERS OF SUCH DROPPED CEILINGS THAT ARE BELOW THE |
| MAIN CEILING LINE SHALL BE OF NONCOMBUSTIBLE MATERIALS, |
| EXCEPT THAT IN TYPE III AND V CONSTRUCTION, |
| FIRE-RETARDANT-TREATED WOOD SHALL BE PERMITTED. THE |
| CONSTRUCTION OF EACH SET-OUT WALL SHALL BE OF |
| FIRE-RESISTANCE-RATED CONSTRUCTION AS REQUIRED |
| ELSEWHERE IN THIS CODE. |
| |
| 6)SHEET A0.12 & S00-01 BOTH INDICATE HEAVY LOADS |
| (DENSE FILING) IN THE TWO FILE ROOMS. NEITHER SHEET |
| INDICATES WHAT LIVE LOADS SEE TABLE 1607.1 PROVIDE |
| MINIMUM CONCENTRATED LIVE LOADS. |
| |
| 7) NOTE; COMMENT# 6 REQUIRES A THRESHOLD INSPECTOR ON |
| SITE SINCE THIS IS A THRESHOLD BUILDING. |
| WPB AMENDMENT 105.13.6. W.P.B. |
| CONSTRUCTION SERVICES DEPARTMENT |
| REQUEST FOR THRESHOLD BUILDINGS A |
| SPECIAL INSPECTOR AS REQUIRED BY S. |
| 553.79(5) FLORIDA STATUTES TO THE MIN- |
| IMUM INSPECTIONS REQUIRED BY THIS CODE. |
| CONTACT HAROLD PISKURA MANAGER OF THE |
| SPECIAL INSPECTOR PROGRAM AT (561) |
| 805-6711 FOR FURTHER INFORMATION BEFORE |
| THE PERMIT MAY BE ISSUED. |
| |
| 8) FL S. S. 553.71(7) " THRESHOLD |
| BUILDING" MEANING ANY BUILDING WHICH IS |
| GREATER THAN (3) STORIES OR 50 FT IN |
| HEIGHT, OR WHICH HAS AN ASSEMBLY OCCUPAN |
| CY CLASSIFICATION AS DEINED IN THE |
| FLORIDA BUILDING CODE WHICH EXCEEDS |
| 5,000 SQ FT IN AREA AND AN OCCUPANT |
| CONTENT OF GREATER THAN 500 PERSONS. |
| 105.13.1 THE ENFORCING AGENCY SHALL |
| REQUIRE A SPECIAL INSPECTOR TO PERFORM |
| STRUCTURAL INSPECTIONS ON A THRESHOLD |
| BUILDING PURSUANT TO A STRUCTURAL |
| INSPECTION PLAN PREPARED BY THE |
| ENGINEER OF RECORD. THE STRUCTURAL |
| INSPECTION PLAN MUST BE SUBMITTED TO THE |
| ENFORCING AGENCY PRIOR TO THE ISSUANCE |
| OF A BUILDING PERMIT FOR THE |
| CONSTRUCTION OF A THRESHOLD BUILDING. |
| THE PURPOSE OF THE STRUCTURL INSPECTION |
| PLAN IS TO PROVIDE SPECIFIC INSPECTION |
| PROCEDURES AND SCHEDULES SO THAT THE |
| BUILDING CAN BE ADEQUATELY INSPECTED FOR COMPLIANCE |
| WITH THE PERMITTED DOCUMENTS. |
| |
| 9)W.P.B. AMENDMENT 105.13.4.4 ALL |
| PLANS FOR THE BUILDING WHICH ARE |
| REQUIRED TO BE SIGNED AND SEALED BY THE |
| ARCHITECT OR ENGINEER OF RECORD CON- |
| TAIN A STATEMENT THAT, TO THE BEST OF |
| THE ARCHITECT'S PR ENGINEER'S KNOWLEDGE, |
| THE PLANS AND SPECIFICATIONS COMPLY WITH |
| THE APPLICABLE FIRE-SAFETY STANDARDS AS |
| DETERMINED BY THE LOCAL AUTHORITY IN |
| ACCORDANCE WITH THIS SECTION AND 633 |
| FLORIDA STATUTE. |
| |
| 10) SINCE WORK ON THE STRUCTURAL FRAME (FLOOR FRAMING) |
| MAKES THIS BUILDING A |
| THRESHOLD BUILDING, (3) SETS OF ALL DOCUMENTS, PLANS |
| SUBMITTALS AND OR REPORTS WILL BE REQUIRED. |
| |
| BUILDING PLAN REVIEW |
| JIM WITMER C. B. O. |
| |
| TEL: (561)805-6715 |
| FAX: (561)659-8026 |
| E-MAIL: [email protected] |