Plan Review Notes For Permit 07030274 |
Permit Number |
07030274 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-03-14 10:58:30 | | | | | NONCOMPLIANT | | | | PLEASE MAKE THE FOLLOWING CORRECTIONS | | FOR CODE COMPLIANCE AND RESUBMIT FOR | | REVIEW. | | | | 1} THE VALUE ON THE APPLICATION MUST | | INCLUDE THE TOTAL COST OF LABOR AND | | MATERIAL FOR THE GENERATOR, EQUIPMENT | | (TRANSFER SWITCHES, PANELS ETC.) | | AND PAD PER 108.3 FBC AS AMENDED. | | INCREASE THE VALUE AT THE COUNTER WHEN | | RESUBMITTING, AND GET A RECEIPT FROM THE | | PERMIT CLERK. | | | | 2} PROVIDE MANUFACTURERS SPECIFICATIONS | | INDICATING RECOMMENDED SETBACKS AND | | ELECTRICAL SPEC'S FOR THE GENERATOR AND | | TRANSFER SWITCH. | | | | 3} PROVIDE A PANEL SCHEDULE FOR THE | | GENERATOR PANEL. 106.3.5.4 FBC AS | | AMENDED. | | | | 4} PLEASE LOCATE ALL SERVICE AND GENERATOR EQUIPMENT ON | | A SITE PLAN, NOT THE SURVEY, METER ENCLOSURE, | | DISCONNECTS, ATS AND PANELS, SO THAT COMPLIANCE WITH | | ARTICLES 225 AND 230 CAN BE REVIEWED. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLAN REVIEW | | 561/805-6718 | | [email protected] | | |
|