Plan Review Notes For Permit 07030203 |
Permit Number |
07030203 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-05-04 09:36:46 | ****************PROVISO**************** | | A} PER FBC-2004 FUEL GAS, SECTION 404.13.3AN | | INSULATED COPPER TRACER WIRE SHALL BE INSTALLED | | ADJACENT TO UNDERGROUND NONMETALLIC GAS PIPING. THE | | TRACER WIRE SIZE SHALL NOT BE LESS THAN 18 AWG AND THE | | INSULATION TYPE SHALL BE SUITABLE FOR DIRECT BURIAL. | | | | B} PER FBC-2004 FUEL GAS SECTION 408.4 A SEDIMENT | | TRAP SHALL BE INSTALLED DOWNSTREAM OF THE EQUIPMENT | | SHUTOFF VALVE AS CLOSE TO THE INLET OF THE EQUIPMENT AS | | PRACTICAL. | | | | C} PER FBC-2004 FUEL GAS, SECTION 409.1 SHUTOFF VALVE | | FOR GENERATOR IS PART OF THE PIPING SYSTEM AND SHALL BE | | FULL SIZE. REDUCE PIPING SIZE AT GENERATOR DUE TO BTU | | LOAD. |
|