Plan Review Notes
Plan Review Notes For Permit 07030203
Permit Number 07030203
Review Stop G
Sequence Number 1
Notes
Date Text
2007-03-16 10:22:57DENIED
 REFERENCE: FBC-2004 FUEL GAS; FBC-2004 CHAPTER 1, THE
 CITY OF WEST PALM BEACH AMENDMENTS;
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN
 REVIEW TO MEET CODE COMPLIANCE:
  
 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL THE ZONING
 ISSUES HAVE BEEN RESOLVED. ON THE RESUBMITTED SURVEY
 PLEASE CLEARLY MARK THE PROPOSED LOCATION OF THE
 GENERATOR. INDICATION OF ALL DIMENSIONS FROM PROPERTY
 LINES AND DISTANCES FROM ADJACENT DWELLING STRUCTURES.
 INDICATION THAT THE GENERATOR EXHAUST IS NOT INSTALLED
 ANY CLOSER THAN TEN FEET FROM ANY OPENING INTO THE
 DWELLING STRUCTURE. THIS INCLUDES DOORS, WINDOWS AND
 ATTIC VENTILATION OPENINGS.
  
 2. PLEASE SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY
 SHOWS ALL CUT SECTIONS OF PIPE
 AND CORRESPONDING LENGTHS PER FBC-2004
 FUEL GAS CODE. CLEARLY INDICATE ON THE RESUBMITTAL THE
 EXISTING GAS PIPE AND NEW GAS PIPE.
  
 3. PLEASE SHOW TYPE OF PIPING MATERIAL BEING
 INSTALLED, ALL PIPE SIZES, (AND THE EDH
 NUMBER OF CORRUGATED STAINLESS STEEL
 TUBING FOR EACH PIPE SIZE BEING USED ON THE RESUBMITTED
 ISOMETRIC.
 NOTE: THE PIPING TO THE GENERATOR NEEDS TO BE INCREASED
 TO 1-1/4" PE DUE TO THE BTU LOAD OF 560,000 TO THE
 GENERATOR. PLEASE REFERENCE THE SUBMITTED
 MANUFACTURER'S SPECIFICATIONS INDICATING THE BTU LOAD
 TO THE GENERATOR.
  
 4. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL) ON
 THE RESUBMITTED ISOMETRIC.
  
 5. PLEASE INDICATE THE BTU LOAD OF EACH APPLIANCE AND
 THE
 TOTAL BTU LOAD ON THE SYSTEM. REFER TO
 THE FBC-2004 FUEL GAS CODE SECS. 401.8
 THRU 402.6.1 AND TABLES 402.4(1) THRU
 402.4(33) ON THE RESUBMITTED ISOMETRIC.
 NOTE: PLEASE INDICATE THE BTU LOAD TO THE GENERATOR ON
 THE RESUBMITTED ISOMETRIC.
  
 6. SHOW THE DISTANCE FROM THE POINT OF
 DELIVERY, (METER), TO THE MOST REMOTE
 OUTLET IN THE BUILDING AND/OR SYSTEM PER
 FBC-2004 FUEL GAS CODE APPENDIX A - USE
 OF CAPACITY TABLES A.3.1(4).
  
 7. PLEASE INDICATE THE DELIVERY PRESSURE (PSI) PER
 FBC-2004 FUEL GAS CODE SEC. 402.2.
 NATURAL GAS SPECIFY .5 PSI OR 2 PSI ON THE RESUBMITTED
 ISOMETRIC.
 NOTE: ON THE SUBMITTED DRAWING THE GAS PRESSURE WAS
 INDICATED AS 0.5 PSI. PLEASE NOTE THE RED LINE
 CORRECTIONS TO THE PE PIPING TO THE GENERATOR. PLEASE
 REFERENCE THE ATTACHED SIZING TABLES TO THE GAS
 COMMENTS INDICATING THE NEED TO INCREASE THE GAS PIPE
 TO THE GENERATOR.
  
 8. FBC-2004 CHAPTER 1,SECTION 106.3.4.2:
 THE PERSON RESPONSIBLE FOR THE DESIGN OF
 THE DRAWING SHALL CLEARLY PRINT AND SIGN
 NAME, AND ALSO DATE DRAWING. PLEASE DO
 THIS PRIOR TO RESUBMITTING.
  
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721