2007-03-16 10:22:57 | DENIED |
| REFERENCE: FBC-2004 FUEL GAS; FBC-2004 CHAPTER 1, THE |
| CITY OF WEST PALM BEACH AMENDMENTS; |
| |
| THE FOLLOWING CORRECTIONS ARE REQUIRED FOR GAS PLAN |
| REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. A GAS PERMIT CAN NOT BE ISSUED UNTIL THE ZONING |
| ISSUES HAVE BEEN RESOLVED. ON THE RESUBMITTED SURVEY |
| PLEASE CLEARLY MARK THE PROPOSED LOCATION OF THE |
| GENERATOR. INDICATION OF ALL DIMENSIONS FROM PROPERTY |
| LINES AND DISTANCES FROM ADJACENT DWELLING STRUCTURES. |
| INDICATION THAT THE GENERATOR EXHAUST IS NOT INSTALLED |
| ANY CLOSER THAN TEN FEET FROM ANY OPENING INTO THE |
| DWELLING STRUCTURE. THIS INCLUDES DOORS, WINDOWS AND |
| ATTIC VENTILATION OPENINGS. |
| |
| 2. PLEASE SUBMIT AN ISOMETRIC DRAWING THAT CLEARLY |
| SHOWS ALL CUT SECTIONS OF PIPE |
| AND CORRESPONDING LENGTHS PER FBC-2004 |
| FUEL GAS CODE. CLEARLY INDICATE ON THE RESUBMITTAL THE |
| EXISTING GAS PIPE AND NEW GAS PIPE. |
| |
| 3. PLEASE SHOW TYPE OF PIPING MATERIAL BEING |
| INSTALLED, ALL PIPE SIZES, (AND THE EDH |
| NUMBER OF CORRUGATED STAINLESS STEEL |
| TUBING FOR EACH PIPE SIZE BEING USED ON THE RESUBMITTED |
| ISOMETRIC. |
| NOTE: THE PIPING TO THE GENERATOR NEEDS TO BE INCREASED |
| TO 1-1/4" PE DUE TO THE BTU LOAD OF 560,000 TO THE |
| GENERATOR. PLEASE REFERENCE THE SUBMITTED |
| MANUFACTURER'S SPECIFICATIONS INDICATING THE BTU LOAD |
| TO THE GENERATOR. |
| |
| 4. PLEASE INDICATE THE TYPE OF GAS, (LP OR NATURAL) ON |
| THE RESUBMITTED ISOMETRIC. |
| |
| 5. PLEASE INDICATE THE BTU LOAD OF EACH APPLIANCE AND |
| THE |
| TOTAL BTU LOAD ON THE SYSTEM. REFER TO |
| THE FBC-2004 FUEL GAS CODE SECS. 401.8 |
| THRU 402.6.1 AND TABLES 402.4(1) THRU |
| 402.4(33) ON THE RESUBMITTED ISOMETRIC. |
| NOTE: PLEASE INDICATE THE BTU LOAD TO THE GENERATOR ON |
| THE RESUBMITTED ISOMETRIC. |
| |
| 6. SHOW THE DISTANCE FROM THE POINT OF |
| DELIVERY, (METER), TO THE MOST REMOTE |
| OUTLET IN THE BUILDING AND/OR SYSTEM PER |
| FBC-2004 FUEL GAS CODE APPENDIX A - USE |
| OF CAPACITY TABLES A.3.1(4). |
| |
| 7. PLEASE INDICATE THE DELIVERY PRESSURE (PSI) PER |
| FBC-2004 FUEL GAS CODE SEC. 402.2. |
| NATURAL GAS SPECIFY .5 PSI OR 2 PSI ON THE RESUBMITTED |
| ISOMETRIC. |
| NOTE: ON THE SUBMITTED DRAWING THE GAS PRESSURE WAS |
| INDICATED AS 0.5 PSI. PLEASE NOTE THE RED LINE |
| CORRECTIONS TO THE PE PIPING TO THE GENERATOR. PLEASE |
| REFERENCE THE ATTACHED SIZING TABLES TO THE GAS |
| COMMENTS INDICATING THE NEED TO INCREASE THE GAS PIPE |
| TO THE GENERATOR. |
| |
| 8. FBC-2004 CHAPTER 1,SECTION 106.3.4.2: |
| THE PERSON RESPONSIBLE FOR THE DESIGN OF |
| THE DRAWING SHALL CLEARLY PRINT AND SIGN |
| NAME, AND ALSO DATE DRAWING. PLEASE DO |
| THIS PRIOR TO RESUBMITTING. |
| |
| |
| ********IMPORTANT INFORMATION******** |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |