2007-03-14 10:40:59 
 NONCOMPLIANT
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS
 FOR CODE COMPLIANCE AND RESUBMIT FOR
 REVIEW.
  
 PLEASE SUBMIT A SITE PLAN INDICATING THE PHYSICAL
 LOCATION OF THE EQUIPMENT WITH REGARD TO THE SERVICE
 AND GENERATOR EQUIPMENT. NOTE: DISCONNECT REQUIRED TO
 BE SERVICE RATED PER 225.36. THIS INCLUDES THE TRANSFER
 SWITCH IF LOCATED AS A MAIN SERVICE DISCONNECTING
 MEANS. ALSO 110.9 FOR AIC RATING.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  