2007-03-10 12:53:41DENIED;
 1. WATER HAMMER ARRESTOR SHOULD BE NEXT TO SUPPLY LINE
 AT SINK NOTIN CEILING PLUMBING CODE SECTION 604.9
 MANUFACTURES SPECIFICATIONS, AS CLOSE TO SOURCE AS
 POSSIBLE.
 2. PAGE A-1 ELEVATIONS FOR BREAK SINK; NO DOORS
 PERMITED IN THE CLEAR FLOOR SPACE OF THE FRONTAL
 APPROACH. PER NEIL MELICK BUILDING OFFICIAL.
 PLUMBING PLAN REVIEW BY;
 JOHN LEECH