Date |
Text |
2007-03-08 11:45:12 | ** UNSAT ** |
| |
| |
| 1) NOTE: PLEASE SEE SCOPE OF WORK AS APPLIED STATES |
| WORK IN SPACE 110A , YET PLANS INDICATE WORK IN BOTH |
| 110A AND 110B |
| |
| 2) NOTE: PLEASE SEE PLANS SHALL INDICATE THE MINIMUM |
| CODES UNDER THE DESIGN. |
| 2004 FBC W/ 2006 REVISIONS. |
| 2005 NFPA-70 |
| |
| 3) NOTE: PLEASE SEE NEW LIGHTING CONTROL DEVICES BEING |
| INSTALLED AS NEW SHALL COMPLY W/ 13-415.1.ABC.1.1 FOR |
| AUTOMATE SHUT OFF. IF NOT PART OF A LIGHTING CONTROL |
| SYSTEM, THEN THIS MUST BE 30MINS MAXIMUM FOR OC TYPE |
| DEVICES. |
| |
| 4) NOTE: PLEASE CLARIFY NEW LIGHTING FIXTURES BEING |
| ADDED AND WHETHER OR NOT THEY COMPLY WITH CHAPTER 13. |
| MUST STATE TYPE. |
| 2004 FBC CHAPTER 13. |
| |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |