Plan Review Notes For Permit 07030187 |
Permit Number |
07030187 |
|
Review Stop |
E |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-03-08 10:48:27 | *** NOTES REDLINEDON PLANS*** | | | | 1)PLANS DO NOT INDICATE THE 2005 NFPA-70. | | | | 2)NEW LIGHTING CONTROL DEVICE IN SUITE 115B SHALL BE AN | | AUTOMATED TYPE TO MEET 13-415.1.ABC.1.1. | | | | | | | | ** ALL LIGHTING AND CONTROLS IN CEILINGS AND EACH SPACE | | ARE EXISTING TO REMAIN AS NOTED ON PLANS. IF ANY OTHER | | LIGHTING OR LIGHTING CONTROLS ARE NEW OTHER THAN AS | | STATED IN NOTE #2 ABOVE, THEN THEY MUST COMPLY WITH THE | | 2004 FBC W/ 2006 REVISONS FOR CHAPTER 13. NO | | EXCEPTIONS. THIS WAS REDLINED ON PLANS TO BE REVISED, | | SUBMITTED FOR REVIEW BEFORE ANY ROUGH ELECTRICAL | | INSPECTION. | | | | 13-415.1.ABC.1.1, .1.2, AND .1.3., 13-415.1.AB.1.1, | | 13-415.2 |
|