 DENIED/INCOMPLETE INFORMATION
  
 THERE IS AN ELECTRICAL "PANEL" SHOWN ON THE ELECTRICAL
 SCHEMATIC. THIS WOULD APPEAR TO BE A "POOL PANEL". IF
 IT IS EXISTING PLEASE INDICATE ON THE PLAN. IF IT IS
 BEING INSTALLED AS PART OF THIS PERMIT, SUBMIT THE
 FOLLOWING DETAILS ON THE PLAN:
  
 PLEASE SUBMIT DETAILS FOR THE PANEL
 SHOWN ON THE SCHEMATIC, FEEDER AND CONDUIT SIZE AND
 TYPE, PANEL RATING AND OCP,
 PANEL SCHEDULE AND COMPUTED LOAD, ETC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  