Date |
Text |
2007-03-13 12:33:49 | ****CORRECTIONS**** |
| |
| SAMANTHA HILL, BUILDING PLANS EXAMINER |
| 561-805-6724 [email protected] |
| |
| FBC FLORIDA BUILDING CODE 2004 WITH 2006 AMENDMENTS FBC |
| R FLORIDA BUILDING CODE 2004 RESIDENTIAL FBC* WITH 2006 |
| AMENDMENTS |
| CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004 |
| |
| 1.)THE PLANS STATE "TRUSS" WITH DETAILS.TRUSS |
| DESIGN AND MANUFACTURE SHALL COMPLY WITH FBC R802.1.6. |
| |
| 2.)TRUSS DESIGN DRAWINGS ARE TO INCLUDE ALL |
| INFORMATION REQUIRED BY FBC R802.1.6.1.TRUSS |
| ENGINEERING IS NOT REQUIRED AT THIS TIME BUT MAY HELP |
| TO SHOW CODE COMPLIANCE.PLANS ARE TO STATE DESIGN |
| CRITERIA FOR THE TRUSSES.PLEASE INCLUDE DESIGN WIND |
| SPEED AND EXPOSURE CATEGORY, SLOPE, DESIGN LOADS |
| 802.1.6.1(5), LUMBER SIZE AND SPECIES, CONNECTION |
| REQUIREMENTS, CONNECTOR LIMITATIONS FROM MANUFACTURER, |
| FASTENING (SIZE AND NUMBER OF FASTENERS). |
| |
| 3.)TRUSSES SHALL BE CONNECTED TO WALL PLATES BY THE |
| USE OF APPROVED CONNECTORS HAVING A RESISTANCE TO |
| DESIGN UPLIFT, LATERAL AND SHEAR FORCES.STATE DESIGN |
| CRITERIA AND SHOW COMPLIANCE. |
| |
| 4.)THE APPLICATION STATES THAT YOU ARE RECONSTRUCTING |
| A FAMILY ROOM, WHICH IMPLIES WORK ON AN ENCLOSED ROOM |
| ATTACHED TO THE RESIDENCE, BUT THE PLAN SUBMITTED SHOWS |
| A FREE STANDING OPEN STRUCTURE.SHOW EXISTING |
| CONDITIONS AS WELL AS THE PROPOSED IMPROVEMENT.THE |
| FLOOR PLAN IS TO SHOW THE LOCATION OF THIS IMPROVEMENT |
| IN RELATION TO THE BUILDING.PROVIDE A FLOOR PLAN OF |
| THE BUILDING, WITH ROOM DESIGNATIONS, ADJACENT TO THIS |
| IMPROVEMENT.THE PLAN SHOULD CLEARLY SHOW HOW EGRESS, |
| ESPECIALLY FROM BEDROOMS, WILL BE AFFECTED BY THIS |
| IMPROVEMENT (OR SHOW THAT IT WILL NOT BE AFFECTED). |
| |
| 5.)FBC*106.3.5, MINIMUM PLAN REVIEW CRITERIA FOR |
| BUILDINGS, SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA |
| AND DOCUMENTS; A FLOOR PLAN, SITE PLAN, FOUNDATION |
| PLAN, FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; AND ALL |
| EXTERIOR ELEVATIONS. |
| |
| 6.)ARE THE COLUMNS PROPOSED OR EXISTING?PROVIDE A |
| STRUCTURAL DETAIL, CONTINUOUS FROM THE FOUNDATION |
| THROUGH THE ROOF. |
| |
| 7.)FBC*106.1.3, BUILDING PLANS ARE TO BE DRAWN TO A |
| MINIMUM OF 1/8? SCALE.NO SCALE SHOWN. |
| |
| 8.)STATE DESIGN CRITERIA FBC R101.1.NO WIND DESIGN |
| CRITERIA WAS PROVIDED.ALSO STATE OTHER APPLICABLE |
| DESIGN CRITERIA SUCH AS DEAD LOADS, LIVE LOADS, ROOF |
| LOADS. |
| |
| 9.)AS THE PLAN WAS DRAWN IN 3 DIMENSION RATHER THAN |
| PLAN VIEW AND ELEVATIONS, THE DETAILS ARE NOT CLEAR. |
| THE PAGES ARE NOT NUMBERED OR LABELED IN ANY WAY.IT |
| IS DIFFICULT TO GIVE A DETAILED LIST AS I?M NOT SURE |
| HOW TO CONVEY TO YOU WHICH DETAIL OR SHEET I?M |
| REFERRING TO.WHEN RESUBMITTING PLANS ARE TO BE |
| ARCHITECTURAL QUALITY, TO SCALE, WITH ALL INFORMATION |
| REQUESTED IN ITEM 5 ABOVE. |
| |
| 10.) THE SECOND SHEET SHOWS "BEAM BASE".NO DIMENSIONS |
| WERE PROVIDED OTHER THAN 51/2", WHAT IS THE WIDTH? |
| LUMBER HAS TWO DIMENSIONS (SUCH AS 2X4).IT SHOWS A |
| LAG SCREW BUT DOES NOT STATE WHERE THE LAG SCREW WILL |
| BE INSTALLED.IT SHOWS A SCREW HOLDING THE BEAM ONTO |
| THE COLUMN, BUT UPLIFT IS NOT ADDRESSED.IT ALSO SHOWS |
| SCREWS ATTACHING A NOTCHED BEAM TO ANOTHER BEAM.IS |
| THE SAME SCREW FOR BOTH?ONE IS GOING INTO CONCRETE, |
| ONE INTO WOOD.IF THE BEAM DEPTH IS 5 1/2", AND THE |
| SCREW IS 5 1/2", IT SEEMS THAT THE SCREW WOULDN'T BE |
| GOING INTO ANYTHING. |
| |
| THE CROSS MEMBERS APPEAR TO BE GOING UP.THIS DETAIL |
| IS NOT CLEAR.THE FIRST SHEET SEEMS TO SHOW A BEAM |
| SPANNING 13 FEET, ANOTHER BEAM WHICH GOES THE OTHER |
| DIRECTION WITH NO SPAN BETWEEN COLUMNS GIVEN.IT IS |
| NOT CLEAR HOW THE TWO BEAMS ARE CONNECTED STRUCTURALLY. |
| I CANNOT DETERMINE HOW THE SECOND SHEET RELATES TO THE |
| FIRST SHEET AS IT SEEMS TO BE GOING ACROSS THE 13 FOOT |
| SPAN, BUT WHERE DO THE TRUSSES SIT?NO INFORMATION IS |
| PROVIDED AS TO HOW THE TRUSSES WILL CONNECT TO THE |
| BEAM. |
| |
| THE SHEET MARKED ?TRUSS? IS NOT CLEAR.DRAWINGS FOR A |
| TRUSS SYSTEM MUST BE REVIEWED PRIOR TO INSTALLATION |
| FBC802.1.6 AND ARE NOT REQUIRED AT THIS TIME.HOWEVER, |
| SUBMITTAL OF THE TRUSS ENGINEERING MAY ASSIST IN |
| SHOWING CODE COMPLIANCE FOR THIS PROJECT. |
| |
| 11.)ROOF SHEATHING IS TO COMPLY WITH FBC R 803. |
| PLEASE SPECIFY SHEATHING AND FASTENING.NOTE THAT NO |
| SHEATHING IS SHOWN ON THE PLAN BUT THE APPLICATION |
| STATES "COVER PLYWOOD".PLANS ARE TO SHOW ALL DETAILS |
| AND COMPONENTS TO BE INSTALLED. |
| |
| 12.)NO ROOF IS SHOWN ON THE PLAN, BUT YOU HAVE |
| REQUESTED A ROOF PERMIT.PLEASE SPECIFY ROOFING |
| MATERIAL ON THE PLAN. |
| |
| 13.)TWO SETS OF ALL DOCUMENTS REQUIRED.ONLY ONE |
| PRODUCT APPROVAL SUBMITTED. |