2007-03-06 08:53:49BUILDING REVIEW CHECKLIST:
 1- IDENTIFY SPECIFIC FLAT ROOF ASSEMBLY TO BE INSTALLED
 AS REQUIRED BY CITY POLICY FOR ROOFING PERMITS. SEE
 ATTACHED COPY.
  
 2- IF SELECTED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #7, THEN NEED TO PROVIDE RAS 117
 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER
 AREAS.CALCULATIONS NEED TO BE DONE AND SIGNED AND
 SEALED BY ARCHITECT, ENGINEER OR REGISTERED ROOF
 CONSULTANT. SEE GENERAL LIMITATION #7 ON LAST PAGE OF
 NOA 03-0827.02 SUBMITTED.
  
 3- IF SELECTED ASSEMBLY IS LIMITED BY GENERAL
 LIMITATION #9, THEN, IT MAY NOT BE USED IN THIS AREA
 BECAUSE ASSEMBLY MAY NOT MEET THE DESIGN PRESSURES
 REQUIRED BY TABLE R301.2(2) OF 2004 FLORIDA RESIDENTIAL
 CODE. AND, NAIL ENHANCING IS NOT ALLOWED. SEE GENERAL
 LIMITATION #9 ON LAS PAGE OF NOA SUBMITTED.
  
 4- PERMIT VALUATION DECLARED ON THE PERMIT APPLICATION
 IS TOO LOW. VALUATION WAS UPDATED. OWES $186.00 FOR
 UPDATED VALUATION. SEC. 108.3 CITY AMENDMENTS TO FBC
 2004.
  
 5- NOTICE OF COMMENCEMENT TO HAVE NAME OF CONTRACTOR
 DOING THE JOB. REVISE NOC AND RECORD IT AS REQUIRED BY
 SEC. 713.13 FLORIDA STATUTE.
  
 JULIO GOMEZ
 BUILDING PLANS EXAMINER
 (561)805-6712