2007-03-05 13:30:39 | BUILDING REVIEW CHECKLIST: |
| 1- FLAT ROOF PRODUCT APPROVAL SUBMITTED IS FOR LIGHT |
| WEIGHT CONCRETE DECK.PROVIDE PRODUCT APPROVAL FOR |
| WOOD DECK APPLICATION.LIGHT WEIGHT CONCRETE DECKS ARE |
| USUALLY FOUND IN COMMERCIAL BUILDINGS NOT IN SINGLE |
| FAMILY RESIDENCES. |
| |
| 2- ON FLAT ROOF PRODUCT APPROVAL CLEARLY IDENTIFY |
| SPECIFIC APPROVED ASSEMBLY THAT IS GOING TO BE |
| INSTALLED AS REQUIRED BY CITY POLICY FOR ROOFING |
| PERMITS. SEE ATTACHED COPY. |
| |
| 3- ON SELECTED APPROVED ASSEMBLY CLEARLY IDENTIFY BASE |
| SHEET FASTENING OPTION. SEE CITY ROOFING PERMITS |
| POLICY. |
| |
| 4- IF SELECTED APPROVED ASSEMBLY IS LIMITED BY GENERAL |
| LIMITATION #7, THEN PROVIDE RAS 117 CALCULATIONS FOR |
| NAIL ENHANCING AT PERIMETER AND CORNER AREAS. NEED TO |
| MEET THE DESIGN PRESSURES OF TABLE R301.2(2) OF 2004 |
| FLORIDA RESIDENTIAL CODE. SEE GENERAL LIMITATION #7 ON |
| LAST PAGE OF NOA. IF GENERAL LIMITATION #7 REQUIRES |
| CALCULATIONS TO BE DONE BY ARCHITECT OR ENGINEER, THEN |
| PROVIDE SIGNED AND SEALED CALCULATIONS. |
| |
| 5- IF SELECTED APPROVED ASSEMBLY IS LIMITED BY GENERAL |
| LIMITATION #9, THEN ASSEMBLY MAY NOT BE INSTALLED IN |
| THIS AREA BECAUSE THE ASSEMBLY MUST MEET THE DESIGN |
| PRESSURES OF TABLE R301.2(2)2004 FLORIDA RESIDENTIAL |
| CODE AND NAIL ENHANCING IS NOT ALLOWED. SEE GENERAL |
| LIMITATION #9 ON LAST PAGE OF NOA. |
| |
| 6- SPECIFY HOW MUCH AREA IS FLAT ROOF AND HOW MUCH AREA |
| ARE SHINGLES TO DETERMINE BUILDING PERMIT VALUATION AS |
| REQUIRED BY SEC. 108.3 CITY AMENDMENTS TO FBC 2004. |
| |