2007-08-28 15:25:59*** DENIED 5TH TIME**
  
 1) NOTE: REVISED SHEET E-2 AND ENERGY CALCULATIONS WERE
 SENT VIA FED EX TO THIS OFFICE. THIS REVIEWER IN ORDER
 TO PROCESS PERMITTING REMOVED OLD SHEETS AND INSERTED
 NEW SHEETS INTO THE SETS OF PLANS.
 THE SHEET E-2 WAS STILL MISSING ONE EM LT HOWEVER THIS
 IS BEING REDLINED ON PLANS AND NO CHANGES ARE NEEDED.
 ** PLEASE SEE HOWEVER ALL THREE COPIES OF THE ENERGY
 CALCULATIONS WERE NOT SIGNED, DATED AND SEALED AS
 REQUIRED UNDER FAC 61G15-23.002 AND FS471.025. PLEASE
 KNOW IN-FACT THESE ACTUALLY CONTAINED A RAISED SEAL
 OVER *PHOTO-COPIED* SIGNATURE AND DATE.
 THESE SUBMITTED WERE NOT ORIGINAL. THIS REVIEWER HAS
 CALLED OCI AND SPOKE TO MR. RICHARD CREAVELLE WHO IS
 THE ELECTRICAL ENGINEER. HE IS GOING TO GET WITH THE
 MECHANICAL ENGINEER AND FED-EX ONCE AGAIN NEW ENERGY
 CALCULATIONS TO THIS OFFICE FOR AM DELIVERY ON 8/29.
 THIS OFFICE CAN ONLY REQUEST FOR ITEMS TO BE DONE PER
 CODE AND REGULATED STATUTES AND ADMINISTRATIVE CODES.
 UNDER FLORIDA STATUTES, THIS OFFICE AND SPECIFICALLY
 THIS REVIEWER IS BOUND BY THE LAWS AND RULES OF THE
 STATE NOT TO ISSUE PERMIT UNTIL FOUND COMPLIANT WITH
 THE ADOPTED CODES AND ALL OTHER RULES AND ORDINANCES
 ADOPTED BY THE STATE.
 PERMIT IS READY TO ISSUE ONCE THESE ARE IN THIS OFFICE
 AND FOUND TO BE CORRECT.
 PLANS WILL BE OUT-FRONT ONCE AGAIN ON HOLD WAITING FOR
 NEW CALCULATIONS.
  
  
 IF THERE ARE ANY QUESTIONS, PLEASE CALL.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW
 561-805-6717
 [email protected]