Plan Review Notes
Plan Review Notes For Permit 07030127
Permit Number 07030127
Review Stop E
Sequence Number 2
Notes
Date Text
2007-06-19 19:43:55*** UNSAT 2ND REVIEW **
  
  
 ** PLEASE SEE THERE ARE ITEMS FROM PREVIOUS REVIEW
 WHICH ARE STILL NOT ADDRESSED.
 ** PLEASE SEE AS NOTED AND STATED ON PREVIOUS REVIEW AS
 INFORMATION IS ONLY JUST NOW BEING SUBMITTED FOR REVIEW
 THERE ARE NEW COMMENTS.
  
  
  
 1) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC
 CHAPTER 13HAS NOT BEEN ACHIEVED ON PLANS FOR CODE
 COMPLIANCE. PLEASE SEE PLANS NOW INDICATE A LIGHTING
 CONTROL PANEL/SYSTEM IS NOW GOING TO BE INSTALLED WHICH
 IS OK, HOWEVER NOT TIME OF SCHEDULING, NO DEVICES FOR
 OVER RIDE OF SYSTEM AT SEPARATE SPACES CONTAINING FLOOR
 TO CEILING HEIGHT PARTITIONS.
 NO TIMES ON OVER RIDES.(MAXIMUM AS STATED PER CODE)
 NO LOCATIONS ON PLANS FOR THESE TYPE(S) OF DEVICES.
 PLEASE SEE THE DEVICES ON LEGEND DO NOT COORDINATE WITH
 PLANS. PLEASE SEE SOME DEVICES ARE SHOWN ON PLANS FOR
 OS TYPE DEVICES YET RESPONSE LETTER MENTIONS THESE ARE
 ALL TO BE REMOVED. IF REMOVED, PLEASE MEET CODE FOR
 DEVICES WHICH ARE REQUIRED.
 PLEASE SEE 13-415.1ABC.1.1, .1.2 AND .1.3.
 ** PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE NOT
 CODE COMPLIANT. PLEASE KNOW AS THE WAS APPLIED FOR
 PERMIT AFTER DECEMBER 8TH, 2006 THE FLA-COM PROGRAMS
 RELEASED FROM THE STATE CONTAINS THE VERSION 3.0 WHICH
 STATES AT THE TOP OF THE SHEET *EFFECTIVE DATE OF
 DECEMBER 8TH, 2006*.
 PLEASE SEE THE NUMBER OF FIXTURES DO NOT CORRELATE WITH
 PLANS.
 PLEASE SEE THE TYPE OF FIXTURES DO NOT CORRELATE WITH
 PLANS.
 PLEASE SEE THE WATTAGE OF FIXTURES DOES NOT CORRELATE
 WITH PLANS.
 PLEASE SEE THE METHOD OF CONTROLS FOR LIGHTING DOES NOT
 CORRELATE.
 PLEASE SEE THE OWNER AGENT IS NOT SIGNED.
 *PLEASE SEE THE FOLLOWING COMMENT #2 WITH RESPECT TO
 SIGNATURE.
 PLEASE SEE AS MOST THE REQUIRED SYSTEM, DEVICES AND
 ENERGY CALCULATIONS ARE NOT COMPLETE OR COMPLIANT A
 REVIEW CAN ONLY BE DONE ON PLANS SUBMITTED.
 13-415.1.AB.1.1, 13.415.2
  
 2) NOTE: AS STATED ON PREVIOUS REVIEW TO PLEASE BE SURE
 TO HAVE THE DESIGNER OF RECORD FOR THE ENERGY
 CALCULATIONS SIGN, DATE AND SEAL THESE AS REQUIRED PER
 13-103.1.1.1
 PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED IN FACT
 CONTAIN A RAISED SEAL OVER A PHOTO-COPIED SIGNATURE ON
 BOTH SETS SUBMITTED. ONE SET IS BEING RETAINED BY THIS
 OFFICE.
 PLEASE SEE FS 471.025, FAC 61G15-23.002
  
 3) NOTE: PLEASE SEE FS 471.025 AS NO SHEETS IN EITHER
 SET OF ELECTRICAL PLANS CONTAINS ANY SIGNATURE, DATE OR
 RAISED SEAL.
 PLEASE SEE FAC 61G15-23.002
  
 4) NOTE: PLEASE SEE PLANS DO NOT INDICATE SUFFICIENT
 LIGHTING FIXTURES WITH BATTERY BACK UP FOR MINIMUM
 LIGHTING LEVELS PER LS 7.8, 7.9.
 PLEASE SEE PLANS APPEARS TO SHOW SOME 2X4 LAY-IN
 FIXTURES WITH A LINE WHICH ARE TYPICALLY THE BATTERY
 BACK UP TYPE FIXTURE HOWEVER THE SYMBOL AND FIXTURE
 LEGEND DOES NOT SHOW A DIFFERENCE BETWEEN THE TWO.
 PLEASE SEE OTHER AREAS WHICH SHOW THE WALL MOUNTED
 BATTERY BACK UP FIXTURES WHICH ARE OK.
 PLEASE SEE COMMENTS FROM THE FIRE MARSHAL.
  
 5) NOTE: PLEASE CLARIFY WHY CONTINUOUS LOADS ARE NOT
 SHOWN ON TRANSFORMER/SERVICE LOADS?
 215.3, 230.42, 220.
  
 6) NOTE: PLEASE CLARIFY ANY METERING DEVICES ARE
 LOCATED ON RISER/SERVICE.
  
 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO
 REPEAT COMMENTS FOR CODE COMPLIANCE. SETS OF PLANS HAVE
 BEEN RETAINED.
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]