2007-06-19 19:43:55 | *** UNSAT 2ND REVIEW ** |
| |
| |
| ** PLEASE SEE THERE ARE ITEMS FROM PREVIOUS REVIEW |
| WHICH ARE STILL NOT ADDRESSED. |
| ** PLEASE SEE AS NOTED AND STATED ON PREVIOUS REVIEW AS |
| INFORMATION IS ONLY JUST NOW BEING SUBMITTED FOR REVIEW |
| THERE ARE NEW COMMENTS. |
| |
| |
| |
| 1) NOTE: PLEASE SEE COMPLIANCE WITH THE 2004 FBC |
| CHAPTER 13HAS NOT BEEN ACHIEVED ON PLANS FOR CODE |
| COMPLIANCE. PLEASE SEE PLANS NOW INDICATE A LIGHTING |
| CONTROL PANEL/SYSTEM IS NOW GOING TO BE INSTALLED WHICH |
| IS OK, HOWEVER NOT TIME OF SCHEDULING, NO DEVICES FOR |
| OVER RIDE OF SYSTEM AT SEPARATE SPACES CONTAINING FLOOR |
| TO CEILING HEIGHT PARTITIONS. |
| NO TIMES ON OVER RIDES.(MAXIMUM AS STATED PER CODE) |
| NO LOCATIONS ON PLANS FOR THESE TYPE(S) OF DEVICES. |
| PLEASE SEE THE DEVICES ON LEGEND DO NOT COORDINATE WITH |
| PLANS. PLEASE SEE SOME DEVICES ARE SHOWN ON PLANS FOR |
| OS TYPE DEVICES YET RESPONSE LETTER MENTIONS THESE ARE |
| ALL TO BE REMOVED. IF REMOVED, PLEASE MEET CODE FOR |
| DEVICES WHICH ARE REQUIRED. |
| PLEASE SEE 13-415.1ABC.1.1, .1.2 AND .1.3. |
| ** PLEASE SEE THE ENERGY CALCULATIONS SUBMITTED ARE NOT |
| CODE COMPLIANT. PLEASE KNOW AS THE WAS APPLIED FOR |
| PERMIT AFTER DECEMBER 8TH, 2006 THE FLA-COM PROGRAMS |
| RELEASED FROM THE STATE CONTAINS THE VERSION 3.0 WHICH |
| STATES AT THE TOP OF THE SHEET *EFFECTIVE DATE OF |
| DECEMBER 8TH, 2006*. |
| PLEASE SEE THE NUMBER OF FIXTURES DO NOT CORRELATE WITH |
| PLANS. |
| PLEASE SEE THE TYPE OF FIXTURES DO NOT CORRELATE WITH |
| PLANS. |
| PLEASE SEE THE WATTAGE OF FIXTURES DOES NOT CORRELATE |
| WITH PLANS. |
| PLEASE SEE THE METHOD OF CONTROLS FOR LIGHTING DOES NOT |
| CORRELATE. |
| PLEASE SEE THE OWNER AGENT IS NOT SIGNED. |
| *PLEASE SEE THE FOLLOWING COMMENT #2 WITH RESPECT TO |
| SIGNATURE. |
| PLEASE SEE AS MOST THE REQUIRED SYSTEM, DEVICES AND |
| ENERGY CALCULATIONS ARE NOT COMPLETE OR COMPLIANT A |
| REVIEW CAN ONLY BE DONE ON PLANS SUBMITTED. |
| 13-415.1.AB.1.1, 13.415.2 |
| |
| 2) NOTE: AS STATED ON PREVIOUS REVIEW TO PLEASE BE SURE |
| TO HAVE THE DESIGNER OF RECORD FOR THE ENERGY |
| CALCULATIONS SIGN, DATE AND SEAL THESE AS REQUIRED PER |
| 13-103.1.1.1 |
| PLEASE SEE THE ENERGY CALCULATIONS AS SUBMITTED IN FACT |
| CONTAIN A RAISED SEAL OVER A PHOTO-COPIED SIGNATURE ON |
| BOTH SETS SUBMITTED. ONE SET IS BEING RETAINED BY THIS |
| OFFICE. |
| PLEASE SEE FS 471.025, FAC 61G15-23.002 |
| |
| 3) NOTE: PLEASE SEE FS 471.025 AS NO SHEETS IN EITHER |
| SET OF ELECTRICAL PLANS CONTAINS ANY SIGNATURE, DATE OR |
| RAISED SEAL. |
| PLEASE SEE FAC 61G15-23.002 |
| |
| 4) NOTE: PLEASE SEE PLANS DO NOT INDICATE SUFFICIENT |
| LIGHTING FIXTURES WITH BATTERY BACK UP FOR MINIMUM |
| LIGHTING LEVELS PER LS 7.8, 7.9. |
| PLEASE SEE PLANS APPEARS TO SHOW SOME 2X4 LAY-IN |
| FIXTURES WITH A LINE WHICH ARE TYPICALLY THE BATTERY |
| BACK UP TYPE FIXTURE HOWEVER THE SYMBOL AND FIXTURE |
| LEGEND DOES NOT SHOW A DIFFERENCE BETWEEN THE TWO. |
| PLEASE SEE OTHER AREAS WHICH SHOW THE WALL MOUNTED |
| BATTERY BACK UP FIXTURES WHICH ARE OK. |
| PLEASE SEE COMMENTS FROM THE FIRE MARSHAL. |
| |
| 5) NOTE: PLEASE CLARIFY WHY CONTINUOUS LOADS ARE NOT |
| SHOWN ON TRANSFORMER/SERVICE LOADS? |
| 215.3, 230.42, 220. |
| |
| 6) NOTE: PLEASE CLARIFY ANY METERING DEVICES ARE |
| LOCATED ON RISER/SERVICE. |
| |
| 7) NOTE: PLEASE SEE FS 553.80(2)(B) WITH RESPECT TO |
| REPEAT COMMENTS FOR CODE COMPLIANCE. SETS OF PLANS HAVE |
| BEEN RETAINED. |
| |
| * ** IMPORTANT** |
| ONCE ALL REVIEWS ARE DONE AND PLANS ARE |
| PICKED UP FOR CORRECTIONS, PLEASE BE |
| SURE TO COMPLETELY REMOVE ALL OLD/VOIDED |
| SHEETS AND ONLY INSERT NEW REVISED |
| SHEETS INTO TWO COMPLETE SETS FOR REVIEW |
| AND STAMPING. DO NOT LEAVE ANY |
| OLD/VOIDED SHEETS IN SETS. |
| PLEASE KNOW ONLY ONE SET OF THE |
| OLD/VOIDED SHEETS SHOULD BE SUBMITTED |
| FOR REFERENCE. |
| THIS WILL HELP IN THE REVIEW PROCESS AND |
| AVOID ANY DELAYS. |
| |
| ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR |
| COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF |
| THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY, |
| NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO |
| NOT HESITATE IN CONTACTING THIS OFFICE AND THIS |
| REVIEWER. |
| |
| DEWEY PALMER |
| ELECTRICAL PLAN REVIEW II |
| CONSTRUCTION SERVICES DEPT. |
| CITY OF WEST PALM BEACH |
| 561-805-6717 |
| [email protected] |