Plan Review Notes
Plan Review Notes For Permit 07030127
Permit Number 07030127
Review Stop P
Sequence Number 1
Notes
Date Text
2007-03-20 06:57:05DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
 FBC-2004 CHAPTER 11
 FLORIDA ADMINISTRATIVE CODE
 FLORIDA STATUTES
  
 1. ALL SHEETS. THE ARCHITECT ADDRESS IN THE TITLE
 BLOCKS DO NOT REFLECT THE ADDRESS INDICATED ON THE
 FLORIDA DBPR WEBSITE. (SEE ATTACHED SHEET). PLEASE
 UPDATE THE WEBSITE INFORMATION OR THE TITLE BLOCKS SO
 THEY CORRELATE. FAC 61G1-16.004(1) & FS 481.2055.
  
 2. SHT A-1 PLAN SHOWS REMOVAL OF THE DRINKING FOUNTAIN.
 PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED. PLEASE
 PROVIDE A DRINKING FOUNTAIN AND INDICATE THE LOCATION.
  
 3. SHT A-1 PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE
 BREAK ROOM SINK. SECTION 11-4.24.5.
  
 4. SHT A-2 ELEVATION A. CABINET DOORS ARE NOT ALLOWED
 IN THE CLEAR FLOOR SPACE. PLEASE DELETE. (PER BLDG
 OFFICIAL).
  
 5. SHT A-3 DETAIL #1 INDICATE CLEARANCE AS REQUIRED IN
 SECTION 11-4.19.2. (29").
  
 6. SHT P-1 DOMESTIC WATER RISER DIAGRAM. WATER HAMMER
 ARRESTORS SHALL BE LOCATED NEAR THE FIXTURE IN AN
 "EFFECTIVE RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH
 201 AND MANUF. INSTALLATION INSTRUCTIONS.
  
 7. SHT P-1. SUBMIT THE MANUF. SPECIFICATIONS FOR THE
 IWH-1. MUST SHOW LISTING. SECTION 106.1.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]