Plan Review Notes For Permit 07030127 |
Permit Number |
07030127 |
|
Review Stop |
P |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-03-20 06:57:05 | DENIED | | REFERENCE: FBC-2004 PLUMBING | | FBC-2004 CHAPTER 1 | | FBC-2004 CHAPTER 11 | | FLORIDA ADMINISTRATIVE CODE | | FLORIDA STATUTES | | | | 1. ALL SHEETS. THE ARCHITECT ADDRESS IN THE TITLE | | BLOCKS DO NOT REFLECT THE ADDRESS INDICATED ON THE | | FLORIDA DBPR WEBSITE. (SEE ATTACHED SHEET). PLEASE | | UPDATE THE WEBSITE INFORMATION OR THE TITLE BLOCKS SO | | THEY CORRELATE. FAC 61G1-16.004(1) & FS 481.2055. | | | | 2. SHT A-1 PLAN SHOWS REMOVAL OF THE DRINKING FOUNTAIN. | | PER TABLE 403.1 A DRINKING FOUNTAIN IS REQUIRED. PLEASE | | PROVIDE A DRINKING FOUNTAIN AND INDICATE THE LOCATION. | | | | 3. SHT A-1 PLEASE SHOW THE CLEAR FLOOR SPACE FOR THE | | BREAK ROOM SINK. SECTION 11-4.24.5. | | | | 4. SHT A-2 ELEVATION A. CABINET DOORS ARE NOT ALLOWED | | IN THE CLEAR FLOOR SPACE. PLEASE DELETE. (PER BLDG | | OFFICIAL). | | | | 5. SHT A-3 DETAIL #1 INDICATE CLEARANCE AS REQUIRED IN | | SECTION 11-4.19.2. (29"). | | | | 6. SHT P-1 DOMESTIC WATER RISER DIAGRAM. WATER HAMMER | | ARRESTORS SHALL BE LOCATED NEAR THE FIXTURE IN AN | | "EFFECTIVE RANGE" NOT IN THE CEILING AS SHOWN. PDI-WH | | 201 AND MANUF. INSTALLATION INSTRUCTIONS. | | | | 7. SHT P-1. SUBMIT THE MANUF. SPECIFICATIONS FOR THE | | IWH-1. MUST SHOW LISTING. SECTION 106.1.1. | | | | REVIEW BY KEN STEVENS | | (561) 805-6721 | | FAX (561) 805-6731 | | E-MAIL [email protected] |
|