2008-04-04 18:25:32 | SLIDING GLASS DOOR SUBMITTAL, BUILDING REVIEW |
| CHECKLIST. |
| REVIEW UNDER FBC2004. |
| |
| 1- PROVIDE COPIES OF PRODUCT APPROVAL FOR SLIDING GLASS |
| DOORS AS REQUIRED BY DCA RULE 9B-72AS REQUESTED ON |
| PREVIOUS COMMENTS.PACKAGE SUBMITTED NOW DOESN'T |
| INCLUDE THE PRODUCT APPROVAL AND THERE IS NOT PRODUCT |
| APPROVAL IN FILE. |
| |
| 2- ENGINEER LETTER BY LUCAS A. TURNER, P.E. REGARDING |
| DOOR ASSEMBLY TO INCLUDE THREE PANELS NEEDS TO PROVIDE |
| ENGINEERING ANALYSIS SHOWING HOW THE MIDDLE PANEL IS |
| TAKEN INTO CONSIDERATION TO RESIST THE DESIGN LOADS. |
| PRODUCT APPROVAL SHOWS THAT TESTED UNIT HAD ONLY TWO |
| PANELS ON EACH SIDE. ASSEMBLYWITH TWO PANELS SHOWS |
| THAT BOTH PANELS MAY BESUPPORTED ON THREE SIDES, |
| WHILEASSEMBLY WITH THREE PANELS SHOWS THAT MIDDLE |
| PANEL MAY BE SUPPORTED ONLY ON TWO SIDES (TOP AND |
| BOTTOM).PLEASE, PROVIDE ENGINEERING ANALYSIS TO SHOW |
| HOW IS THIS ISSUE ADDRESSED. SEC. 106.1.2 CITY |
| AMENDMENTS TO FBC 2004 TO VERIFY COMPLIANCE WITH SEC. |
| R301 OF 2004 FLORIDA RESIDENTIAL CODE. |
| |
| ***NOTE: IF YOU HAVE ANY QUESTIONS REGARDING THIS |
| ISSUE, PLEASE CONTACT ROBERT BROWN AT (561)805-6652, |
| SINCE I SHARED THIS ISSUE WITH HIM BECAUSEI AM GOING |
| TO BE AWAY FROMTHE OFFICE UNTIL APRIL 14TH. |
| |
| 3- REMAINDER: |
| PLEASE PROVIDE ALL INFORMATION REQUESTED ON PROVISO |
| DATED 7/27/07TO AVOID UNNECESSARY DELAYS IN THE |
| CERTIFICATE OF OCCUPANCY PROCESS.SEE ATTACHED COPY OR |
| REVIEWIT ON-LINE. |
| |