Plan Review Notes
Plan Review Notes For Permit 07030070
Permit Number 07030070
Review Stop P
Sequence Number 1
Notes
Date Text
2007-03-28 11:18:02DENIED
 REFERENCE:
 ** FBC-2004 PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
  
  
 THE FOLLOWING CORRECTIONS/INFORMATION IS REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 CHAPTER 1 SECTION 106.1.1: INFORMATION
 ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
 NOTE: THE SUBMITTED SANITARY ISOMETRIC RISER DIAGRAM ON
 SHEET A6 DOES NOT REFLECT THE FLOOR PLAN ON SHEET A2.
 PLEASE REFERENCE SHEET A2 WITH THIS PLAN REVIEWERS RED
 LINE UNDERGROUND SANITARY SYSTEM INDICATING THE
 FOLLOWING.
  
 A} CABANA BATH: LAV IS INDICATED ON THE WRONG SIDE OF
 THE WATER CLOSET.
  
 B} THE UNDERGROUND BRANCH TO THE KITCHEN IS INDICATED
 IN THE WRONG PLACE.
  
 C} THE UNDERGROUND BRANCH TO BATH #3 IS INDICATED IN
 THE WRONG PLACE.
  
 D} BATH #3: LAV IS MISSING FROM THE SANITARY ISOMETRIC
 RISER DIAGRAM.
  
 E} HER BATH: DOES NOT REFLECT THE FLOOR PLAN.
  
 F} HER BATH: VENT REQUIRED FOR SHOWER PER FBC-2004
 PLUMBING SECTION 901.2.1 AND TABLE 906.1.
  
 G} UTIL. (LAUNDRY ROOM): DOES NOT REFLECT THE FLOOR
 PLAN.
  
 2. SHEET A6 KITCHEN: IS IT THE INTENT TOINSTALL A 7'
 TO 8' WASTE ARM FOR THE DOUBLE BOWL KITCHEN SINK WITH
 DISHWASHER DUE TO THE FACT THAT THERE IS A SNACK BAR
 LOCATED THERE. IT IS SUGGESTED THAT AN AIR ADMITTANCE
 VALVE (STUDOR VENT) BE INSTALLED IN THIS AREA. PER
 FBC-2004 PLUMBING TABLE 906.1 A 2" FIXTURE DRAIN WITH
 AN 1-1/2" TRAP CAN ONLY BE 6' FROM THE VENT. PLEASE
 CLAIFY THIS ON THE RESUBMITTAL.
  
 3. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.4: PLEASE
 SIZE ALL SANITARY PLUMBING AND FIXTURE TRAPS.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved