Plan Review Notes For Permit 07030070 |
Permit Number |
07030070 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-03-19 08:47:43 | *** DENIED *** | | 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, SEE | | FBC 13-600.3.A, 12-8-06 REV. | | | | 2) COOLING LOAD CALCULATIONS FOR A/C #3 ARE CALLING FOR | | 25,246 SENSIBLE BTU'S, MECHANICAL PLANS FOR A/C #3 ARE | | CALLING FOR 43,700 SENSIBLE BTU'S, THE PLANS CAN ONLY | | CALL FOR 15% MORE THAN THE COOLING LOAD CAL'S, SEE 2004 | | FBC13-607.1.ABC.1.1, 12-8-06 REV. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. | | |
|