Plan Review Notes
Plan Review Notes For Permit 07030070
Permit Number 07030070
Review Stop M
Sequence Number 1
Notes
Date Text
2007-03-19 08:47:43*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM 600A-04R, SEE
 FBC 13-600.3.A, 12-8-06 REV.
  
 2) COOLING LOAD CALCULATIONS FOR A/C #3 ARE CALLING FOR
 25,246 SENSIBLE BTU'S, MECHANICAL PLANS FOR A/C #3 ARE
 CALLING FOR 43,700 SENSIBLE BTU'S, THE PLANS CAN ONLY
 CALL FOR 15% MORE THAN THE COOLING LOAD CAL'S, SEE 2004
 FBC13-607.1.ABC.1.1, 12-8-06 REV.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.
  