Plan Review Notes
Plan Review Notes For Permit 07020797
Permit Number 07020797
Review Stop M
Sequence Number 1
Notes
Date Text
2007-03-05 12:26:40*** DENIED ***
 1) SHOW SEER OF A/C SYSTEMS ON PLANS.
  
 2) SHOW HOW RETURN AIR IS REACHING SECOND FLOOR AIR
 HANDLER UNIT.
  
 3) ALL INFORMATION, DRAWINGS, SPECIFICATIONS AND
 ACCOMPANYING DATA SHALL BEAR THE PRINTED NAME AND
 SIGNATURE OF THE PERSON RESPONSIBLE FOR THE DESIGN. PER
 FBC 104.2.1.
  
 4)ALL OF THE RETURN AIR TRANSFER DUCTS ARE TO SMALL,
 SEE 2004 FBC/R M1602.4 (A) AND (C) EXCEPT.
  
 *** 2004 FBC/R M1602.4.
 BALANCED RETURN AIR MAY BE ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
 (C)HABITABLE ROOMS ONLY SHALL BE
 REQUIRED TO MEET THESE REQUIREMENTS FOR
 PROPER BALANCED RETURN AIR EXCLUDING
 BATHROOMS, CLOSETS, STORAGE ROOMS AND
 LAUNDRY ROOMS, EXCEPT THAT ALL SUPPLY
 AIR INTO THE MASTER SUITE SHALL BE
 INCLUDED. PER 2004 FBC/R M1602.4 .
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved