Plan Review Notes
Plan Review Notes For Permit 07020773
Permit Number 07020773
Review Stop P
Sequence Number 2
Notes
Date Text
2007-10-31 10:56:43DENIED 2ND TIME
 REFERENCE:
 ** FBC-2004 WITH 05 & 06 REVISIONS, PLUMBING.
 ** FBC-2004 CHAPTER 1, THE CITY OF
 WEST PALM BEACH AMENDMENTS.
 ** FLORIDA ADMINISTRATIVE CODE (FAC).
 ** FLORIDA STATUTES (FS).
  
 THE FOLLOWING CORRECTIONS/INFORMATION ARE REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE ON THE
 RESUBMITTED PLANS:
  
 1. REFERENCE MECHANICAL COMMENTS #1 & 2 ON THE ENERGY
 CALCULATIONS.
  
 2. PER FBC-2004 CHAPTER 1, SECTION 106.3.5.1.3,
 PLUMBING: AN ISOMETRIC POTABLE WATER RISER DIAGRAM IS
 REQUIRED FOR BOTH THE HOT AND COLD WATER INDICATING THE
 PIPE SIZES, VALVE LOCATIONS, LOCATION OF THE WATER
 SUPPLY LINE WITH THE BACKFLOW PREVENTER **608, THERMAL
 EXPANSION CONTROL **607.3FOR THE WATER HEATER, AND
 THE LOCATION OF THE WATER-HAMMER ARRESTORS **604.9
 WHERE QUICK CLOSING VALVES ARE UTILIZED (WASHING
 MACHINES, DISHWASHERS, ICE MAKERS).
  
 END OF COMMENTS:
  
 REVIEW BY: MIKE PERSON
 PLUMBING PLANS EXAMINER