Plan Review Notes
Plan Review Notes For Permit 07020773
Permit Number 07020773
Review Stop M
Sequence Number 2
Notes
Date Text
2007-10-19 16:06:25PLAN REVIEW UNDER THE 2004 FLORIDA BUILDING CODE &
 REFERENCED CODES WITH 05, 06 REVISIONS, CITY OF WEST
 PALM BEACH AMENDMENTS TO CHAPTER 1 (W.P.B.), FLORIDA
 ADMINISTRATIVE CODE (F.A.C.), AND FLORIDA STATUTES
 (F.S.).
  
 *** DENIED ***
 1) PLEASE SUBMIT ENERGY CALCULATIONSUSING FORM
 600A-04-"R" OR 600B-04-"R" OR 600C-04-"R", SEE 2004 FBC
 13-600.0, AND FBC/EXISTING 611.1.
  
 2) WHEN RE-SUBMITTING HAVE THE NEW ENERGY CALCULATIONS
 SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC
 13-600.3.ABC.2.
  
 3) THE CLOTHES DRYER VENT MAY NOT DISCHARGE ON TO THE
 A/C CONDENSER UNIT, SEE 2004 FBC/M 501.2 AND FBC RES.
 R303.4.2 .
  