Plan Review Notes
Plan Review Notes For Permit 07020773
Permit Number 07020773
Review Stop P
Sequence Number 1
Notes
Date Text
2007-03-12 16:08:09DENIED
 REFERENCE: FBC-2004 PLUMBING; FBC-2004 CHAPTER 1, CITY
 OF WEST PALM BEACH AMENDMENTS;
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 CHAPTER 1, 106.1.1 INFORMATION ON
 CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
 NOTE: THE SUBMITTED SANITARY ISOMETRIC RISER DIAGRAM ON
 SHEET 7 DOES NOT REFLECT THE FLOOR PLAN.
 A} PLEASE CORRECT AND RESUBMIT THE SANITARY RISER
 DIAGRAM INDICATING THE DOUBLE BOWL KITCHEN SINK WITH
 DISHWASHER AND THE CORRECT LOCATION OF THE LAVATORY OFF
 BEDROOM #2.
  
 B} 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 NOTE: PLEASE CORRECT THE BRANCH DRAIN AND STACK TO BE
 THREE INCH (3") ON THE RESUBMITTAL.
  
 C} 802.4 STANDPIPES.STANDPIPES SHALL BE INDIVIDUALLY
 TRAPPED. STANDPIPES SHALL
 EXTEND A MINIMUM OF 18 INCHES (457MM)
 AND A MAXIMUM OF 42 INCHES (1066MM)
 ABOVE THE TRAP WEIR. ACCESS SHALL BE
 PROVIDED TO ALL STANDPIPES AND DRAINS FOR RODDING.
 NOTE: PLEASE INDICATE THE STANDPIPE ON THE
 RESUBMITTAL.
  
  
 D} 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 NOTE: PLEASE INDICATE THE TWO-WAY CLEANOUT ON THE
 RESUBMITTAL.
  
 E} 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 NOTE: CLEANOUT FOR THE WASHING MACHINE SHALL BE THREE
 INCH (3"). PLEASE INDICATE THIS ON THE RESUBMITTAL.
  
 F} 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: CLEANOUT FOR THE WASHING MACHINE TO BE LOCATED AT
 FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.). PLEASE
 INDICATE THIS ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  