Plan Review Notes For Permit 07020773 |
Permit Number |
07020773 |
|
Review Stop |
M |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-03-09 16:04:18 | *** DENIED *** | | 1) ENERGY CALCULATIONS NEED TO BE ON FORM600A-04-R, | | SEE 2004 FBC 13-600.3.A (12-8-06 REVISION). | | | | 2) WHEN RE-SUBMITTING HAVE THE NEW ENERGY CALCULATIONS | | SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC | | 13-600.3.ABC.2. | | | | 3) THE CLOTHES DRYER VENT MAY NOT DISCHARGE ON TO THE | | A/C CONDENSER UNIT, SEE 2004 FBC/M 501.2 . | | | | 4) THE 10" RETURN AIR TRANSFER DUCTS TO THE BEDROOMS | | NEED TO BE 12". | | *** 2004 FBC/R M1602.4 .BALANCED RETURN AIR MAY BE | | ACHIEVED BY. | | (A)TRANSFER DUCTS MAY ACHIEVE THIS BY | | INCREASING THE RETURN TRANSFER ONE AND | | ONE HALF TIMES THE CROSS SECTIONAL AREA | | (SQUARE INCHES) OF THE SUPPLY DUCT | | ENTERING THE ROOM OR SPACE IT'S SERVING | | AND THE DOOR HAVING AT LEAST AN | | UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE | | PROPER RETURN AIR BALANCE. | | | | MECHANICAL PLAN REVIEW BY; | | TOM GORDON (561) 805-6729. |
|