Plan Review Notes
Plan Review Notes For Permit 07020773
Permit Number 07020773
Review Stop M
Sequence Number 1
Notes
Date Text
2007-03-09 16:04:18*** DENIED ***
 1) ENERGY CALCULATIONS NEED TO BE ON FORM600A-04-R,
 SEE 2004 FBC 13-600.3.A (12-8-06 REVISION).
  
 2) WHEN RE-SUBMITTING HAVE THE NEW ENERGY CALCULATIONS
 SIGNED BY OWNER/AGENT ALSO, PER 2004 FBC
 13-600.3.ABC.2.
  
 3) THE CLOTHES DRYER VENT MAY NOT DISCHARGE ON TO THE
 A/C CONDENSER UNIT, SEE 2004 FBC/M 501.2 .
  
 4) THE 10" RETURN AIR TRANSFER DUCTS TO THE BEDROOMS
 NEED TO BE 12".
 *** 2004 FBC/R M1602.4 .BALANCED RETURN AIR MAY BE
 ACHIEVED BY.
 (A)TRANSFER DUCTS MAY ACHIEVE THIS BY
 INCREASING THE RETURN TRANSFER ONE AND
 ONE HALF TIMES THE CROSS SECTIONAL AREA
 (SQUARE INCHES) OF THE SUPPLY DUCT
 ENTERING THE ROOM OR SPACE IT'S SERVING
 AND THE DOOR HAVING AT LEAST AN
 UNRESTRICTED 1 INCHUNDERCUT TO ACHIEVE
 PROPER RETURN AIR BALANCE.
  
 MECHANICAL PLAN REVIEW BY;
 TOM GORDON (561) 805-6729.