Plan Review Notes
Plan Review Notes For Permit 07020762
Permit Number 07020762
Review Stop B
Sequence Number 2
Notes
Date Text
2007-04-07 11:03:31****CORRECTIONS****
  
 SAMANTHA HILL, BUILDING PLANS EXAMINER
 561-805-6724 [email protected]
  
 FBC FLORIDA BUILDING CODE 2004
 FBC R FLORIDA BUILDING CODE 2004 RESIDENTIAL
 FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE FBC2004
  
 1.)PLEASE REVISE THE INSTALLATION SCHEDULE.IT
 SPECIFIES 1.5INCH SPACING, ENGINEER SPECIFIES 7INCH,
 PRODUCT APPROVAL REQUIRES 3INCH MINIMUM INTO CONCRETE.
 ENGINEER HAS NOT ADDRESSED MINIMUM ANCHOR SPACING FOR
 STEEL SUSBSTRATES.
  
 2.)SEE ATTACHED SAMPLE INSTALLATION SCHEDULE.THE
 FORM YOU ARE USING DOES NOT HAVE A SUBSTRATE PER
 OPENING.IT APPEARS THAT TWO ARE STEEL; WHAT ARE THE
 OTHER TWO?
  
  