Plan Review Notes For Permit 07020762 |
Permit Number |
07020762 |
|
Review Stop |
B |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-03-20 13:18:19 | ****CORRECTIONS**** | | | | SAMANTHA HILL, BUILDING PLANS EXAMINER | | 561-805-6724 [email protected] | | | | FBCFLORIDA BUILDING CODE 2004 | | FBC EBEXISTING BUILDING CODE 2004 | | FBC R RESIDENTIAL 2004 | | FBC* CITY OF WEST PALM BEACH AMENDMENTS TO THE | | FBC2004 | | | | 1.)DOCUMENTS PREPARED BY AN ENGINEER AND SUBMITTED | | FOR PUBLIC RECORD ARE TO BE SIGNED, SEALED, DATED | | ORIGINALS FAC61G15-23 (SITE SPECIFIC ENGINEERING). | | | | 2.)PAGE 14 OF THE PRODUCT APPROVAL SPECIFIES A | | MINIMUM SPACING OF 3" TO 3.5" DEPENDING ON ANCHOR TYPE. | | THE ENGINEER HAS SPECIFIED 1.5" ANCHOR SPACING INTO | | METAL.PLEASE JUSTIFY THIS ANCHOR SPACING; HOW CAN | | THIS ANCHOR SPACING BE ACCEPTABLE FOR THIS APPLICATION | | WHEN THE ENGINEER FOR THE PRODUCT HAS SPECIFIED A 3" | | MINIMUM FOR OTHER ANCHORS?THIS CORRECTION IS NOT A | | STATEMENT THAT THE 1.5" IS UNACCEPTABLE; IT IS A | | REQUEST FOR DOCUMENTATION THAT MINIMUM ANCHOR SPACING | | HAS BEEN ADDRESSED. | | | | 3.)PRODUCT APPROVALS ARE TO BE APPROVED BY DESIGNER | | OF RECORD, FBC*106.3.3. | | | | |
|