Plan Review Notes
Plan Review Notes For Permit 07020699
Permit Number 07020699
Review Stop P
Sequence Number 1
Notes
Date Text
2007-03-21 15:41:08DENIED
 REFERENCE: FBC-2004 SECTIONS 424.2 OR R4101 SWIMMING
 POOLS; FBC-2004 CHAPTER 1, THE CITY OF WEST PALM BEACH
 AMENDMENTS; FLORIDA ADMINISTRATIVE CODE;
  
 THE FOLLOWING CORRECTION/INFORMATION IS REQUIRED FOR
 PLUMBING PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106.1 SUBMITTAL
 DOCUMENTS. CONSTRUCTION
 DOCUMENTS, SPECIAL INSPECTION AND
 STRUCTURAL OBSERVATION PROGRAMS, AND
 OTHER DATA SHALL BE SUBMITTED IN TWO OR
 MORE SETS WITH EACH APPLICATION FOR A
 PERMIT.
 NOTE: ONLY ONE SET OF CONSTRUCTION DOCUMENTS WERE
 SUBMITTED.
  
 2. PER FLORIDA ADMINISTRATIVE CODE AND FBC-2004
 CHAPTER 1, SECTION 106.1:
 FAC-61G15-23.002 SEAL SIGNATURE AND DATE
 SHALL BE AFFIXED:
 EACH SHEET OF PLANS AND PRINTS WHICH
 MUST BE SEALED UNDER PROVISIONS OF
 CHAPTER 471 SHALL BE SEALED, SIGNED AND
 DATED BY THE PROFESSIONAL ENGINEER IN
 RESPONSIBLE CHARGE. ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME, ADDRESS,
 AND LICENSE NUMBER ON EACH SHEET. IF
 PRACTICING THROUGH A DULY AUTHORIZED
 ENGINEERING BUSINESS, ENGINEERS SHALL
 LEGIBLY INDICATE THEIR NAME LICENSE NUM-
 BER, AS WELL AS, THE NAME, ADDRESS, AND CERTIFICATE OF
 AUTHORIZATION NUMBER OF
 THE ENGNEERING BUSINESS ON EACH SHEET.
 NOTE: AFFXED SEAL IS WEAK.
  
 3. PLEASE CORRELATE THE VENT SIZE. THE VENT TABLE
 MAXIMUM LENGTH TABLE INDICATES A 1" VENT. THE PIPING
 SCHEMATIC AND THE MAIN DRAIN DETAIL INDICATE A 1-1/2"
 VENT. PLEASE CORRECT AND CORRELATE THE VENT SIZE ON THE
 RESUBMITTAL.
  
 4. COMPLY WITH FBC-2004 SEC 424.2, OR
 FBCR-2004 SEC R4101 PRIVATE SWIMMING
 POOLS.
 (PLEASE ADD TO NOTES ON THE RESUBMITTAL)
  
 5. FBC-2004 SEC. 424.2.14.1, OR
 FBCR-2004 SEC. R4101.14.1 SWIMMING POOL
 WATER HEATERS SHALL BEAR THE LABEL OF A
 RECOGNIZED TESTING AGENCY. (MANUFACTURE
 SHEETS REQUIRED, PLEASE SUBMIT)
  
 6. FBC-2004 SEC. 424.2.14.2, OR
 FBCR-2004 SEC. R4101.14.2 WATER
 RETENTION, PROVIDE A POSITIVE MEANS OF
 RETAINING WATER IN THE HEATER WHEN PUMP
 IS SHUT OFF.(MANUFACTURE SHEETS
 REQUIRED, PLEASE SUBMIT)
  
 7. THE POOL DATA & EQUIPMENT, AND SWIMMING POOL PLAN
 SEEM INCOMPLETE. THERE ARE NO MAIN DRAINS, INLETS,
 SKIMMER, CLEANER LINE OR VACUUM FITTING (OPTIONAL)
 INDICATED FOR THE POOL. PER FBC-2004 SECTION 424.2.6.2
 REQUIRED EQUIPMENT: EVERY SWIMMING POOL SHALL BE
 EQUIPPED COMPLETE WITH APPROVED MECHANICAL EQUIPMENT
 CONSISTING OF FILTER, PUMP, PIPING VALVES AND COMPONENT
 PARTS. PLEASE CLARIFY THE FILTER CYCLE INDICATED AS
 2.55 HRS IS THIS FOR THE POOL OR THE SPA OR FOR BOTH.
 PLEASE CLARIFY AND CORRECT ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION********
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721