Notes |
Date |
Text |
2007-03-15 07:22:44 | | | DENIED/INCOMPLETE INFORMATION | | | | 1} PLEASE SUBMIT DETAILS FOR THE PANEL | | SHOWN ON THE SCHEMATIC, FEEDER AND CONDU | | IT SIZE AND TYPE, PANEL RATING AND OCP, | | PANEL SCHEDULE AND COMPUTED LOAD, ETC. | | IF AN ELECTRIC HEATER IS TO BE INSTALLED | | PLEASE SUBMIT CALCULATIONS FOR THE MAINSERVICE. IF | | THE PANEL IS EXISTING, PLEASE INDICATE SAME ON THE | | SCHEMATIC, HAVE THE ENGINEER OF RECORD INITIAL SAME. | | | | 2} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL | | SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO | | BE IMPOSED BY THE ADDITION OF THE NEW POOL AND HEATER | | EQUIPMENT. 215.5 NEC 2005. | | | | 3}TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR | | REVIEW PER 106.1 FBC AS AMENDED. | | | | IF THERE ARE ANY QUESTIONS PLEASE CALL. | | | | BILL TROBAUGH | | ELECTRICAL PLANS EXAMINER | | CITY OF WEST PALM BEACH | | 561/805-6718 | | [email protected] |
|