Plan Review Notes
Plan Review Notes For Permit 07020699
Permit Number 07020699
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-15 07:22:44 
 DENIED/INCOMPLETE INFORMATION
  
 1} PLEASE SUBMIT DETAILS FOR THE PANEL
 SHOWN ON THE SCHEMATIC, FEEDER AND CONDU
 IT SIZE AND TYPE, PANEL RATING AND OCP,
 PANEL SCHEDULE AND COMPUTED LOAD, ETC.
 IF AN ELECTRIC HEATER IS TO BE INSTALLED
 PLEASE SUBMIT CALCULATIONS FOR THE MAINSERVICE. IF
 THE PANEL IS EXISTING, PLEASE INDICATE SAME ON THE
 SCHEMATIC, HAVE THE ENGINEER OF RECORD INITIAL SAME.
  
 2} PROVIDE A LOAD CALCULATION FOR THE ELECTRICAL
 SERVICE, INDICATING ALL EXISTING LOADS AND ALL LOADS TO
 BE IMPOSED BY THE ADDITION OF THE NEW POOL AND HEATER
 EQUIPMENT. 215.5 NEC 2005.
  
 3}TWO SETS OF ALL DOCUMENTS MUST BE SUBMITTED FOR
 REVIEW PER 106.1 FBC AS AMENDED.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  
 BILL TROBAUGH
 ELECTRICAL PLANS EXAMINER
 CITY OF WEST PALM BEACH
 561/805-6718
 [email protected]