Plan Review Notes For Permit 07020687 |
Permit Number |
07020687 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-03-12 15:16:44 | -*****APPROVED***** | | | | SHEETS FP-2, FP-3, AND FP-4 WERE STAMPED, INTIALED, AND | | DATED.READY FOR PERMIT ISSUANCE. | | | | | | **REMINDERS** | | | | 1.WATERFLOW ACTIVATION SHALL INTIATE A GENERAL ALARM | | WITHIN 45 TO 60 SECONDS. | | | | 2.SPRINKLER SYSTEM IS TO BE MONITORED. | | | | 3.ELECTRONIC SWITCHES IN ADDITION TO CHAIN AND LOCK | | IS REQUIRED FOR DOUBLE CHECK DETECTOR ASSEMBLY. | | COORDINATE WITH THE GENERAL AND/OR FIRE ALARM CONTRATOR | | BY FINAL SPRINKLER/FIRE ALARM INSPECTION. |
|