Plan Review Notes For Permit 07020664 |
Permit Number |
07020664 |
|
Review Stop |
G |
Sequence Number |
2 |
|
Notes |
Date |
Text |
2007-03-27 11:15:38 | ****************PROVISO**************** | | A} IF DRYER ROOM IS A CONFINED SPACE, OPENINGS | | REQUIRED PER SECTION 304.5 ORSECTION 304.6 SHALL BE | | INSTALLED.MINIMUM 1,300 CUBIC FEET REQUIRED. | | | | B}FUTURE GENERATOR GAS PIPING AT OWN RISK, SEPERATE | | GEN/RES PERMIT REQUIRED WITH ZONING APPROVAL OF | | GENERATOR PLACEMENT. | | NOTE: PER FBC-2004 FUEL GAS SECTION, 404.12 OUTLET | | CLOSURES. GAS OUTLETS THAT DO NOT CONNECT TO APPLIANCES | | SHALL BE CAPPED GAS TIGHT. IF GAS DELIVERY PRESSURE IS | | 2 PSI OR GREATER MP REGULATORS SHALL BE INSTALLED PRIOR | | TO FINAL INSPECTION. |
|