2007-03-05 17:04:39*****DENIED*****
  
  
  
  
 1.THE COMPLETE ADDRESS OF WHERE THE SCOPE OF WORK IS
 BEING CONDUCTED SHALL BE IN THE TITLE BLOCK OF EACH
 SUBMITTED PLAN SHEET.
  
 2.THE NUMERICAL ADDRESS IS REQUIRED. ON LOCATION
 SECTION OF HYDRAULIC DESIGN INFORMATION SHEET.
  
 3.THE SPECIFICATION SHEET FOR THE STYLE 009 FIRELOCK
 EZ RIGID COUPLING HAS THE STAMPING OF THE TOWN OF
 JUPITER.ALL SUCH PAPERWORK WILL BE STAMPED BY THE
 (AHJ) CITY OF WEST PALM BEACH.
  
 4.PLEASE PROVIDE SAFETY MARGIN CALCULATION FOR THIS
 SYSTEM.AS PER WEST PALM BEACH FIRE PREVENTION, A
 SAFETY MARGIN OF NO LESS THAN 5.0 PSI IS REQUIRED.
  
  
 TO EXPEDITE THE PLAN REVIEW PROCESS , INCLUDE A
 RESPONSE LETTER INDICATING HOW/WHERE EACH COMMENT WAS
 ADDRESSED
  
  