Date |
Text |
2007-07-06 09:52:17 | DENIED |
| REFERENCE: FBC-2004 PLUMBING |
| FBC-2004 CHAPTER 1 |
| |
| ****FROM PREVIOUS REVIEW |
| |
| 1. OK |
| |
| 2. SHT P1.1 THE RISER DIAGRAM DOES NOT REFLECT THE |
| FLOOR PLAN.TWO FLOOR SINKS AND A FLOOR CLEANOUT SHOWN |
| ON THE RISER DIAGRAM ARE NOT SHOWN ON THE RISER |
| DIAGRAM.--THE SINK IN THE CABINET IS SHOWN ON THE |
| LEFT SIDE OF THE BUILDING DRAIN LINE ON THE FLOOR PLAN, |
| BUT ON THE RIGHT SIDE OF THE DRAIN LINE ON THE RISER |
| DIAGRAM.--THE FLOOR PLAN SHOWS A LINE FROM THE |
| 3-COMPARTMENT SINK TO THE BRANCH LINE TO THE MOP SINK |
| AND A DRAINAGE LINE FROM THE LAV TO THE BRANCH LINE TO |
| THE MOP SINK. THESE LINES ARE NOT INDICATED ON THE |
| RISER DIAGRAM.PLEASE CORRELATE THE INFORMATION |
| BETWEEN THE RISER AND THE FLOOR PLAN. SECTION 106.1.1. |
| (SEE RED LINE MARK-UP ON ONE SET OF P1.1). |
| ****THE LAV SHALL CONNECT TO THE SANITARY RISER DIAGRAM |
| AS WAS INDICATED ON THE TOILET ROOM RISER DIAGRAM FIRST |
| SUBMITTED. THE INTENT WAS TO HAV THE LAV TO THE GREASE |
| SYSTEM DELETED FROM THE FLOOR PLAN. ONLY GREASE LADEN |
| WASTE SHALL DISCHARGE INTO THE GREASE SYSTEM. THE LAV |
| WILL ACT AS THE WET VENT FOR THE TOILET ROOM. |
| |
| 3. OK |
| 4. OK |
| 5. OK |
| |
| 6. SHT P1.1 THE DOMESTIC WATER RISER DIAGRAM INDICATES |
| AN ICE MAKER. AN INDIRECT WASTE RECEPTOR IS REQUIRED |
| FOR THE DRAINAGE OF THE ICE MAKER. PLEASE INDICATE THE |
| LOCATION OF THE ICE MAKER AND THE FLOOR SINKON THE |
| FLOOR PLAN. SECTION 106.1.1. A WATER HAMMER ARRESTOR IS |
| REQUIRED ON THE SUPPLY TO THE ICE MAKER. SECTION |
| 604.9. |
| ****RESPONSE NOTED, BUT THE WATER HAMMER ARRESTOR SHALL |
| BE LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" NOT |
| IN THE CEILING AS SHOWN. PDI-WH 204 & MANUFACTURE |
| INSTALLATION INSTRUCTIONS. |
| |
| 7. OK |
| |
| ****NEW COMMENT: |
| |
| 1B. THE STAMPED PLANS FROM DBPR ARE NOW NOT SUBMITTED. |
| PLEASE SUBMIT THE ORIGINAL SHEETS A1.1 IN THE NEW SETS |
| OF PLANS BEING SUBMITTED AND INDICATE THAT THEY ARE FOR |
| "REFERENCE TO THE DBPR REVIEW" AND TO SEE REVISED SHEET |
| A1.1 FOR ALL OTHERAPPROVED INFORMATION. SECTION |
| 102.2.1. |
| |
| REVIEW BY KEN STEVENS |
| (561) 805-6721 |
| FAX (561) 805-6731 |
| E-MAIL [email protected] |