Plan Review Notes
Plan Review Notes For Permit 07020640
Permit Number 07020640
Review Stop P
Sequence Number 2
Notes
Date Text
2007-07-06 09:52:17DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 ****FROM PREVIOUS REVIEW
  
 1. OK
  
 2. SHT P1.1 THE RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN.TWO FLOOR SINKS AND A FLOOR CLEANOUT SHOWN
 ON THE RISER DIAGRAM ARE NOT SHOWN ON THE RISER
 DIAGRAM.--THE SINK IN THE CABINET IS SHOWN ON THE
 LEFT SIDE OF THE BUILDING DRAIN LINE ON THE FLOOR PLAN,
 BUT ON THE RIGHT SIDE OF THE DRAIN LINE ON THE RISER
 DIAGRAM.--THE FLOOR PLAN SHOWS A LINE FROM THE
 3-COMPARTMENT SINK TO THE BRANCH LINE TO THE MOP SINK
 AND A DRAINAGE LINE FROM THE LAV TO THE BRANCH LINE TO
 THE MOP SINK. THESE LINES ARE NOT INDICATED ON THE
 RISER DIAGRAM.PLEASE CORRELATE THE INFORMATION
 BETWEEN THE RISER AND THE FLOOR PLAN. SECTION 106.1.1.
 (SEE RED LINE MARK-UP ON ONE SET OF P1.1).
 ****THE LAV SHALL CONNECT TO THE SANITARY RISER DIAGRAM
 AS WAS INDICATED ON THE TOILET ROOM RISER DIAGRAM FIRST
 SUBMITTED. THE INTENT WAS TO HAV THE LAV TO THE GREASE
 SYSTEM DELETED FROM THE FLOOR PLAN. ONLY GREASE LADEN
 WASTE SHALL DISCHARGE INTO THE GREASE SYSTEM. THE LAV
 WILL ACT AS THE WET VENT FOR THE TOILET ROOM.
  
 3. OK
 4. OK
 5. OK
  
 6. SHT P1.1 THE DOMESTIC WATER RISER DIAGRAM INDICATES
 AN ICE MAKER. AN INDIRECT WASTE RECEPTOR IS REQUIRED
 FOR THE DRAINAGE OF THE ICE MAKER. PLEASE INDICATE THE
 LOCATION OF THE ICE MAKER AND THE FLOOR SINKON THE
 FLOOR PLAN. SECTION 106.1.1. A WATER HAMMER ARRESTOR IS
 REQUIRED ON THE SUPPLY TO THE ICE MAKER. SECTION
 604.9.
 ****RESPONSE NOTED, BUT THE WATER HAMMER ARRESTOR SHALL
 BE LOCATED NEAR THE FIXTURE IN AN "EFFECTIVE RANGE" NOT
 IN THE CEILING AS SHOWN. PDI-WH 204 & MANUFACTURE
 INSTALLATION INSTRUCTIONS.
  
 7. OK
  
 ****NEW COMMENT:
  
 1B. THE STAMPED PLANS FROM DBPR ARE NOW NOT SUBMITTED.
 PLEASE SUBMIT THE ORIGINAL SHEETS A1.1 IN THE NEW SETS
 OF PLANS BEING SUBMITTED AND INDICATE THAT THEY ARE FOR
 "REFERENCE TO THE DBPR REVIEW" AND TO SEE REVISED SHEET
 A1.1 FOR ALL OTHERAPPROVED INFORMATION. SECTION
 102.2.1.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]


Account Summary | Usage Policy | Privacy Policy
Copyright © 2005 – 2014, SunGard Pentamation, Inc & City of West Palm Beach, FL – All Rights Reserved