Notes
Date Text
2007-03-17 16:51:35DENIED
 REFERENCE: FBC-2004 PLUMBING
 FBC-2004 CHAPTER 1
  
 1. SHT A1.1 FLOOR PLAN KEYNOTE #2 NOT SHOWN ON THE
 FLOOR PLAN. PLEASE CLARIFY. SECTION 106.1.1.
  
 2. SHT P1.1 THE RISER DIAGRAM DOES NOT REFLECT THE
 FLOOR PLAN.TWO FLOOR SINKS AND A FLOOR CLEANOUT SHOWN
 ON THE RISER DIAGRAM ARE NOT SHOWN ON THE RISER
 DIAGRAM.--THE SINK IN THE CABINET IS SHOWN ON THE
 LEFT SIDE OF THE BUILDING DRAIN LINE ON THE FLOOR PLAN,
 BUT ON THE RIGHT SIDE OF THE DRAIN LINE ON THE RISER
 DIAGRAM.--THE FLOOR PLAN SHOWS A LINE FROM THE
 3-COMPARTMENT SINK TO THE BRANCH LINE TO THE MOP SINK
 AND A DRAINAGE LINE FROM THE LAV TO THE BRANCH LINE TO
 THE MOP SINK. THESE LINES ARE NOT INDICATED ON THE
 RISER DIAGRAM.PLEASE CORRELATE THE INFORMATION
 BETWEEN THE RISER AND THE FLOOR PLAN. SECTION 106.1.1.
 (SEE RED LINE MARK-UP ON ONE SET OF P1.1).
  
 3. SHT P1.1 THE GREASE LINE UPSTREAM OF THE GREASE
 INTERCEPTOR IS LABELED AS A SANITARY LINE. PLEASE
 CORRECT. SECTION 106.1.1.
  
 4. SHT P1.1 THE INLET AND OUTLET PIPING FOR THE GREASE
 INTERCEPTOR REQUIRES A 2-WAY CLEANOUT ON EACH PIPE.
  
 5. SHT P1.1 PLUMBING NOTES #1 INDICATES THE CODE
 REFERENCE AS FBC-2001. PLANS SHOULD INDICATE FBC-2004
 AS THE DESIGN CODE.
  
 6. SHT P1.1 THE DOMESTIC WATER RISER DIAGRAM INDICATES
 AN ICE MAKER. AN INDIRECT WASTE RECEPTOR IS REQUIRED
 FOR THE DRAINAGE OF THE ICE MAKER. PLEASE INDICATE THE
 LOCATION OF THE ICE MAKER AND THE FLOOR SINKON THE
 FLOOR PLAN. SECTION 106.1.1. A WATER HAMMER ARRESTOR IS
 REQUIRED ON THE SUPPLY TO THE ICE MAKER. SECTION
 604.9.
  
 7. THE GREASE INTERCEPTOR SHALL BE SIZED BY THE
 ENVIRONMENTAL COMPLIANCE MANAGER. PLEASE CONTACT RODNEY
 COMPO @ (561) 822-2272, OR FAX (561) 822- 2287, OR
 E-MAIL [email protected]. FOR A DETERMINATION. SECTION III
 OF THE MUNICIPAL CODE.
  
 REVIEW BY KEN STEVENS
 (561) 805-6721
 FAX (561) 805-6731
 E-MAIL [email protected]