Plan Review Notes For Permit 07020640 |
Permit Number |
07020640 |
|
Review Stop |
FIRE |
Sequence Number |
1 |
|
Notes |
Date |
Text |
2007-03-30 14:29:01 | ***DENIED*** | | | | 1) FOOD THAT PRODUCES GREASE LADEN SMOKE AND VAPORS | | SHALL BE PROTECTED BY AN APPROVED HOOD/SUPPRESSION | | SYSTEM IN ACCORDANCE WITH NFPA 96. SEPARATE SHOP | | DRAWINGS AND PERMITS REQUIRED FOR HOOD AND SUPPRESSION | | SYSTEMS. PLEASE CLARIFY HOW EXISTING SYSTEM WILL BE | | IMPACTED BY THIS WORK. | | | | 2) SEPARATE SHOP DRAWINGS REQUIRED FOR FIRE SPRINKLER | | AND FIRE ALARM REMODEL. | | | | 3) "K" TYPE FIRE EXTINGUISHER IS REQUIRED IN KITCHEN | | AREA. | | | | 4)ANY DOOR IN A MEANS OF EGRESS SERVING AN OCCUPANT | | LOAD OF 100 OR GREATER THAN 100 PERSONS, SHALL COMPLY | | WITH NFPA 101, SEC. 12.2.2.2.3, AND SHALL BE PROVIDED | | WITH PANIC HARDWARE. | | | | 5) 2A-10B,C RATED FIRE EXTINGUISHERS SHALL BE PROVIDED | | IN LOCATIONS NOT TO EXCEED 75' TRAVEL DISTANCE TO REACH | | AN EXTINGUISHER. | | | | | | MIKE WENNERGREN, ASSISTANT FIRE MARSHAL | | FIRE PLAN REVIEW | | FIRE PREVENTION (561) 805-6722 |
|