Plan Review Notes
Plan Review Notes For Permit 07020640
Permit Number 07020640
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-04 14:24:16** UNSAT **
  
 1) NOTE: PLEASE KNOW THAT PERMIT APPLICATION HAS BEEN
 SUBMITTED AFTER DECEMBER 8TH, 2006 WHICH PLACES
 PROJECTS UNDER THE NEW CODES ADOPTED BY THE STATE.
 PLEASE SEE THAT THIS SHALL INCLUDE 2006 REVISIONS TO
 THE 2004 FBC FOR ALL TRADES AND THE 2005 NFPA-70.
 PLEASE KNOW THERE ARE CHANGE SIN THE FBC WHICH WILL
 AFFECT DESIGNS FOR ALL TRADES.
 PLEASE ALSO SEE ELECTRICAL CHANGES UNDER THE 2005
 INCLUDING ANY SECTIONS OF CODES WHICH ARE REFLECTED ON
 PLANS FROM THE PREVIOUS 2002 NEC.
 PLEASE LIST THE FOLLOWING FOR THIS REVIEWER AT A
 MINIMUM.
 2004 FBC W/ 2006 REVISIONS.
 2005 NFPA-70
 2002 NFPA-72
 2003 NFPA-101
  
 2) NOTE:PLEASE SUBMIT ENERGY/PERFORMANCE CALCULATIONS
 FOR NEW LIGHTING.
 PLEASE KNOW THAT ALL NEW SHALL COMPLY WITH THE CHAPTER
 13 REQUIREMENTS.
 PLEASE BE SURE ONCE THE METHOD OF CONTROLS IS FIGURED
 FOR THE PLANS TO BE SURE TO CORRELATE CONTROL METHODS
 ON THE ENERGY CALCULATIONS/PERFORMANCE CALCULATIONS.
 PLEASE SEE FBC 2004 W/ 2006 REVISIONS. 13-103.1.1.1,
 13-415.1.ABC.1.1, .1.2, .1.3, 13-415.1.AB.1.1,
 13-415.2.
  
 3) NOTE: PLEASE SEE THAT PLANS DO NOT INDICATE ANY
 METHODS FOR THE REQUIRED AUTOMATED CONTROLS PER FBC
 2004 W/2006 REVISIONS. ANY NEW AREAS, LIGHTING AND
 CONTROLS.
 THE SCOPE OF WORK AS NOTED AND SHOWN ON PLANS WILL
 REQUIRE CHAPTER 13 COMPLIANCE FOR CONTROLS AND
 LIGHTING.
 13-415.1.ABC.1.1, .1.2 AND .1.3.
  
 4) NOTE: PLEASE PROVIDE LOCATIONS FOR ELECTRICAL PANELS
 WHETHER NEW OR EXISTING ALONG WITH TRANSFORMER
 LOCATION.
 PLEASE KNOW AT THIS TIME ONE PANEL IS BEING NOTED AS
 BEING PLACED IN A STORAGE ROOM WHICH IS NOT PERMITTED.
 PLEASE SEE THE LOCATION AND MINIMUM CLEARANCES FOR THE
 ELECTRICAL PANEL(S) NEED TO MEET 110.26.
 PLEASE ALSO SEE 408.7 AND 240.24 FOR LOCATION OF EASILY
 IGNITABLE MATERIALS AND CLOSE PROXIMITY OF COMBUSTIBLES
 WITH OVER CURRENT PROTECTION DEVICES.
 PLEASE ADJUST PLANS.
 PLEASE SEE 450.9, 450.13, 450.21 FOR TRANSFORMER
 LOCATIONS.
  
 5) NOTE:PLEASE SEE PANELS SEEMS TO BE NOTED AS
 EXISTING; HOWEVER THE RISER DOES NOT SEEM TO SHOW WHAT
 IS EXISTING OR WHAT IS NEW.
 PLEASE CLARIFY.
 FBC 106.1.2, 106.3.5.1.2
  
 6) NOTE: PLEASE KNOW WHETHER NEW OR EXISTING THE PANEL
 ON THE SECONDARY SIDE OF THE TRANSFORMER WILL REQUIRE A
 MCB IF NOT EXISTING.
 PLEASE ALSO SEE THE TAP CONDUCTOR RULES AS STATED IN
 240.21C
 PLEASE ALSO SEE 408.16
  
 7) NOTE: PLEASE SEE PLANS MENTIONS TO REMOVE ALL HORNS
 AND STROBES, PLEASE BE SURE TO NOTE ON PLANS THAT ANY
 NEW DEVICES BEING RE-INSTALLED SHALL MEET FBC
 11-4.28.1,.2 AND .3(4). PLEASE STATE LEVELS FOR THESE
 DEVICES FOR ADA COMPLIANCE.
 PLEASE KNOW ANY OLD DEVICES WHICH MAY NOT MEET CODE
 WILL NOT BE PERMITTED TO BE RE-INSTALLED. NEW DEVICES
 WILL BE REQUIRED.
  
 8) NOTE: PLEASE CLARIFY THE RECEPTACLE DEVICES IN
 KITCHEN/FOOD AREAS MEETING 210.8B3
  
 9) NOTE: PLEASE CLARIFY THE NOTE ON PANEL *PB* WHICH
 MENTIONS 2-POLE 40AMP BREAKER ON #10 CONDUCTORS ALONG
 WITH 6 ADDITIONAL #10 CONDUCTORS IN ONE SINGLE 1/2 INCH
 CONDUIT. PLEASE SEE TABLES IN CHAPTER 9 AS PIPE FILL IS
 EXCEEDED. (C.1)
  
 10) NOTE: PLEASE KNOW IF THE SCOPE OF ELECTRICAL WORK
 IS THE INSTALLATION OF THE SERVICE EQUIPMENT AS SHOWN
 ON RISER AND ALL SERVICE EQUIPMENT DOES NOT EXIST AT
 PRESENT AND IS NEW, THEN THE PLANS WILL BE REQUIRED TO
 BE SIGNED, DATED AND SEALED BY A PE. FS
 471.003(2)(H)(2A)
  
 11) NOTE: PLEASE SHOW GROUNDING ATTACHMENT FOR THE
 TRANSFORMER IF NEW.
 250.20, 250.30, 250.66
  
 12) NOTE: PLEASE NOTE IF EM/EXT LTS ARE WIRED PER
 700.12E (LOCAL LIGHTING BRANCH CIRCUIT).
  
 * ** IMPORTANT**
 ONCE ALL REVIEWS ARE DONE AND PLANS ARE
 PICKED UP FOR CORRECTIONS, PLEASE BE
 SURE TO COMPLETELY REMOVE ALL OLD/VOIDED
 SHEETS AND ONLY INSERT NEW REVISED
 SHEETS INTO TWO COMPLETE SETS FOR REVIEW
 AND STAMPING. DO NOT LEAVE ANY
 OLD/VOIDED SHEETS IN SETS.
 PLEASE KNOW ONLY ONE SET OF THE
 OLD/VOIDED SHEETS SHOULD BE SUBMITTED
 FOR REFERENCE.
 THIS WILL HELP IN THE REVIEW PROCESS AND
 AVOID ANY DELAYS.
  
 ** PLEASE BE SURE TO CALL IF THERE ARE ANY QUESTIONS OR
 COMMENTS WITH RESPECT TO THE TYPED COMMENTS ABOVE. IF
 THERE ARE ANY COMMENTS WHICH ARE NOT CLEAR IN ANY WAY,
 NOT UNDERSTOOD OR NOT TYPED IN A CLEAR MANOR, PLEASE DO
 NOT HESITATE IN CONTACTING THIS OFFICE AND THIS
 REVIEWER.
  
 DEWEY PALMER
 ELECTRICAL PLAN REVIEW II
 CONSTRUCTION SERVICES DEPT.
 CITY OF WEST PALM BEACH
 561-805-6717
 [email protected]