2007-03-12 14:55:28DENIED
 REFERENCE: FBC-2004 PLUMBING
  
 SHEET 12, SANITARY ISOMETRIC RISER DIAGRAM: THE
 FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING PLAN
 REVIEW TO MEET CODE COMPLIANCE:
 (A) 406.3 WASTE CONNECTIONS.THE TRAP AND
 FIXTURE DRAIN FOR AN AUTOMATIC CLOTHES
 WASHER SHALL BE A MINIMUM OF 2 INCHES
 (51MM) IN DIAMETER. THE AUTOMATIC
 CLOTHES WASHER FIXTURE DRAIN SHALL
 CONNECT TO A BRANCH DRAIN OR DRAINAGE
 STACK A MINIMUM OF 3 INCHES (76MM) IN
 DIAMETER.
 NOTE: SIZE OF BRANCH DRAIN IS WRONG FOR WASHING
 MACHINE. PLEASE CORRECT AND RESUBMIT.
  
 (B) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM)
 NOTE: CLEANOUT FOR WASHING MACHINE TO BE THREE INCH
 (3"). PLEASE INDICATE THIS ON THE RESUBMITTAL.
  
 (C) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: CLEANOUT FOR WASHING MACHINE TO BE LOCATED FOUR
 FEET ABOVE FINNISH FLOOR (4' A.F.F.). PLEASE INDICATE
 THIS ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  