Plan Review Notes
Plan Review Notes For Permit 07020619
Permit Number 07020619
Review Stop B
Sequence Number 1
Notes
Date Text
2007-04-05 15:42:39BUILDING PLAN REVIEW
 PERMIT: 07020619
 ADD: 1369 9TH STREET
 CONT: RAMDEEN JACQUELINE
 TEL: (561)856-6655
 FL BLD CODE= 2004 FLORIDA BUILDING CODE
 W/ 2006 FBC REVISIONS
 * WEST PALM BEACH AMENDMENTS
  
 REVIEW 1ST
 ACTION: DENIED
  
 1)--- VERY IMPORTANT STATEMENT ---
 PLEASE DO NOT IGNORE!
 WHEN RESUBMITTING PLANS PLEASE INDICATE
 THE REVISION & REMOVE & REPLACE ANY
 PAGES AS NECESSARY. A TRANSMITTAL LETTER
 LISTING THE ORIGINAL REVIEW COMMENT NUM-
 BER, WITH A DESCRIPTION OF THE REVISION
 MADE, IDENTIFYING THE SHEET OR SPECIFICA
 TION PAGE WHERE THE CHANGES CAN BE FOUND
 WILL HELP TO EXPEDITE YOUR PERMIT. THANK
 YOU FOR YOUR ANTICIPATED COOPERATION.
  
 2)BEFORE A PERMIT TO CONSTRUCT, MAY
 BE ISSUED, IMPACT FEES MUST BE PAID TO
 PALM BEACH COUNTY. THE ACTUAL PERMIT
 SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT
 ATTACHED TO THE PERMIT APPLICATION.
 PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 3) FL S S 713.13
 NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF
 THE COURT.
 NOTE: 713.13(2)
 IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS
 NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE
 RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE:
 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT
 THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION.
  
 4)106.3.3*THOSE PRODUCTYS WHICH ARE REGULATED BY
 THE CCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN
 WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL
 FOR JURISDICTIONAL APPROVAL. NOTE: THE PRODUCT APPROVAL
 FOR THE WINDOW IS MISSING FROM THE PACKAGE.
  
 5) FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF
 SUFFICIENT CLARITY TO INDICATE THE LOACTION, NATURE AND
 EXTENT OF THE WORK PROPOSED. PAGE #3 INDICATES A WOODEN
 STRUCTURE, HOWEVER, PAGE #7 INDICATES MASONRY BLOCK.
 STATE WHICH TYPE OF MATERIAL WILL BE USED FOR THE
 PROPOSED ADDITION.
  
 6)R802.1.6TRUSS DESIGN DRAWINGS, PREPARED IN
 CONFORMANCE WITH SEC.R802.1.6.1 SHALL BE PROVIDED TO
 THE BUILDING OFFICIAL AND APPROVED PRIOR TO
 INSTALLATION.
  
 7)SHOW A DETAIL DRAWING HOW THE NEW ROOF WILL TIE
 INTO THE EXISTING ROOF.
  
 8)R807.1 IN BUILDINGS WITH COMBUSTIBLE CEILING OR
 ROOF CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE
 PROVIDED TO ATTIC AREA THAT EXCEED 30 SQUARE FEET AND
 HAVE A FERTICA HEIGHT OF 30 INCHES OR GRATER. THE ROUGH
 FRAMED OPENING SHALL NOT BE LESS THAN 22 INCHES BY 30
 INCHES.
  
 9)R806.1 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES
 FORMED WHERE CEILINGS ARE APPLIED DIRECTLY TO THE
 UNDERSIDE OF ROOF RAFTERS SHALL HAVE CROSS VENTILATION
 FOR EACH SEPARATE SPACE BY VENTILATING OPENINGS
 PROTECTED AGAINST THE ENTRANCE OF RAIN. INDICATE THIS
 REQUIREMENT ON THE ROOF FRAMINGDRAWINGS.
  
 MYRON JACOBS
 BUILDING PLAN REVIEWER
 805-6726
  
  
  
  
  