2007-04-05 15:42:39 | BUILDING PLAN REVIEW |
| PERMIT: 07020619 |
| ADD: 1369 9TH STREET |
| CONT: RAMDEEN JACQUELINE |
| TEL: (561)856-6655 |
| FL BLD CODE= 2004 FLORIDA BUILDING CODE |
| W/ 2006 FBC REVISIONS |
| * WEST PALM BEACH AMENDMENTS |
| |
| REVIEW 1ST |
| ACTION: DENIED |
| |
| 1)--- VERY IMPORTANT STATEMENT --- |
| PLEASE DO NOT IGNORE! |
| WHEN RESUBMITTING PLANS PLEASE INDICATE |
| THE REVISION & REMOVE & REPLACE ANY |
| PAGES AS NECESSARY. A TRANSMITTAL LETTER |
| LISTING THE ORIGINAL REVIEW COMMENT NUM- |
| BER, WITH A DESCRIPTION OF THE REVISION |
| MADE, IDENTIFYING THE SHEET OR SPECIFICA |
| TION PAGE WHERE THE CHANGES CAN BE FOUND |
| WILL HELP TO EXPEDITE YOUR PERMIT. THANK |
| YOU FOR YOUR ANTICIPATED COOPERATION. |
| |
| 2)BEFORE A PERMIT TO CONSTRUCT, MAY |
| BE ISSUED, IMPACT FEES MUST BE PAID TO |
| PALM BEACH COUNTY. THE ACTUAL PERMIT |
| SET OF PLANS MUST BE STAMPED BY THAT |
| OFFICE, AND A COPY OF THE PAID RECEIPT |
| ATTACHED TO THE PERMIT APPLICATION. |
| PLEASE CALL (561)233-5025 FOR MORE |
| INFORMATION. |
| |
| 3) FL S S 713.13 |
| NOTICE OF COMMENCEMENT, TO BE FILED WITH THE CLERK OF |
| THE COURT. |
| NOTE: 713.13(2) |
| IF THE WORK DESCRIBED IN THE NOTICE OFCOMMENCEMENT IS |
| NOT ACTUALLYCOMMENCED WITHIN 90 DAYS AFTER THE |
| RECORDING THEREOF, SUCH NOTICE IS NULL & VOID. NOTE: |
| 713.13(6)THE POSTING OF THE NOTICE OF COMMENCEMENT AT |
| THE CONSTRUCTION SITE BEFORE THE FIRST INSPECTION. |
| |
| 4)106.3.3*THOSE PRODUCTYS WHICH ARE REGULATED BY |
| THE CCA RULE 9B-72 SHALL BE REVIEWED AND APPROVED IN |
| WRITING BY THE DESIGNER OF RECORD PRIOR TO SUBMITTAL |
| FOR JURISDICTIONAL APPROVAL. NOTE: THE PRODUCT APPROVAL |
| FOR THE WINDOW IS MISSING FROM THE PACKAGE. |
| |
| 5) FBC 106.1.1 CONSTRUCTION DOCUMENTS SHALL BE OF |
| SUFFICIENT CLARITY TO INDICATE THE LOACTION, NATURE AND |
| EXTENT OF THE WORK PROPOSED. PAGE #3 INDICATES A WOODEN |
| STRUCTURE, HOWEVER, PAGE #7 INDICATES MASONRY BLOCK. |
| STATE WHICH TYPE OF MATERIAL WILL BE USED FOR THE |
| PROPOSED ADDITION. |
| |
| 6)R802.1.6TRUSS DESIGN DRAWINGS, PREPARED IN |
| CONFORMANCE WITH SEC.R802.1.6.1 SHALL BE PROVIDED TO |
| THE BUILDING OFFICIAL AND APPROVED PRIOR TO |
| INSTALLATION. |
| |
| 7)SHOW A DETAIL DRAWING HOW THE NEW ROOF WILL TIE |
| INTO THE EXISTING ROOF. |
| |
| 8)R807.1 IN BUILDINGS WITH COMBUSTIBLE CEILING OR |
| ROOF CONSTRUCTION, AN ATTIC ACCESS OPENING SHALL BE |
| PROVIDED TO ATTIC AREA THAT EXCEED 30 SQUARE FEET AND |
| HAVE A FERTICA HEIGHT OF 30 INCHES OR GRATER. THE ROUGH |
| FRAMED OPENING SHALL NOT BE LESS THAN 22 INCHES BY 30 |
| INCHES. |
| |
| 9)R806.1 ENCLOSED ATTICS AND ENCLOSED RAFTER SPACES |
| FORMED WHERE CEILINGS ARE APPLIED DIRECTLY TO THE |
| UNDERSIDE OF ROOF RAFTERS SHALL HAVE CROSS VENTILATION |
| FOR EACH SEPARATE SPACE BY VENTILATING OPENINGS |
| PROTECTED AGAINST THE ENTRANCE OF RAIN. INDICATE THIS |
| REQUIREMENT ON THE ROOF FRAMINGDRAWINGS. |
| |
| MYRON JACOBS |
| BUILDING PLAN REVIEWER |
| 805-6726 |
| |
| |
| |
| |
| |