Plan Review Notes
Plan Review Notes For Permit 07020611
Permit Number 07020611
Review Stop P
Sequence Number 1
Notes
Date Text
2007-03-12 14:12:49DENIED
 REFERENCE: FBC-2004 PLUMBING; FBC-2004 CHAPTER 1, CITY
 OF WEST PALM BEACH AMENDMENTS;
  
 THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING
 PLAN REVIEW TO MEET CODE COMPLIANCE:
  
 1. PER FBC-2004 CHAPTER 1, SECTION 106.1.1 INFORMATION
 ON CONSTRUCTION
 DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL
 BE OF SUFFICIENT CLARITY TO INDICATE THE
 LOCATION, NATURE AND EXTENT OF THE WORK
 PROPOSED AND SHOW IN DETAIL THAT IT WILL
 CONFORM TO THE PROVISIONS OF THIS CODE
 AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS,
 AS DETERMINED BY THE
 BUILDING OFFICIAL.
  
 2. SHEET PG.2, SANITARY ISOMETRIC RISER DIAGRAM: PER
 FBC-2004 CHAPTER 1, SECTION 106.3.5.4 RESIDENTIAL (ONE
 AND TWO-FAMILY) PLEASE SUBMIT A PLUMBING SANITARY
 ISOMETRIC RISER DIAGRAM INDICATING ALL WASTE, VENTS,
 TRAPS AND SIZES WITH CLEANOUT LOCATIONS.
 NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC, IS NOT
 CODE COMPLIANT, AND DOES NOT REFLECT THE FLOOR PLAN.
 PLEASE REFERENCE THE ATTACHED CORRECTED SANITARY
 ISOMETRIC RISER DIAGRAM TO THE PLUMBING COMMENTS FOR
 THE RESUBMITTAL.
  
 3. SHEET PG. 2, SANITARY ISOMETRIC RISER DIAGRAM: PER
 FBC-2004 PLUMBING, SECTION 1002.1 A FIXTURE SHALL NOT
 BE DOUBLE TRAPPED. A WATER CLOSET HAS AN INTEGRAL TRAP
 AND A TRAP NEED NOT BE INDICATED.
  
 4. SHEET PG. 2, SANITARY ISOMETRIC RISER DIAGRAM: PER
 FBC-2004 PLUMBING, SECTION 1002.1 EACH PLUMBING FIXTURE
 SHALL BE SEPERATELY TRAPPED BY A WATER SEAL TRAP.
 NOTE: TRAP REQUIRED FOR TUB.
  
 5. SHEET PG.2, SANITARY ISOMETRIC RISER DIAGRAM:
 (A) 708.3.5 BUILDING DRAIN AND BUILDING
 SEWER JUNCTION. THERE SHALL BE A
 CLEANOUT NEAR THE JUNCTION OF THE
 BUILDING DRAIN AND THE BUILDING SEWER.
 NOTE: PLEASE INDICATE THS CLEANOUT AS A TWO-WAY
 CLEANOUT.
  
 (B) 708.7 MINIMUM SIZE. CLEANOUTS SHALL
 BE THE SAME NOMINAL SIZE AS THE PIPE
 THEY SERVE UP TO 4 INCHES (102MM).
 NOTE: FULL SIZE CLEANOUT (3") REQUIRED FOR WASHING
 MACHINE.
  
 (C) 708.9 ACCESS. ACCESS SHALL BE
 PROVIDED TO ALL CLEANOUTS.
 NOTE: CLEANOUT FOR WASHING MACHINE SHALL BE LOCATED
 FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.)
  
 6. SHEET PG. 2, SANITARY ISOMETRIC RISER DIAGRAM: PER
 FBC-2004 PLUMBING, SECTION 406.3 STANDPIPE REQUIRED FOR
 WASHING MACHINE. PLEASE INDICATE ON THE RESUBMITTAL.
  
 ********IMPORTANT INFORMATION
 IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING,
 PLEASE REPLACE ONLY SHEETS
 WHICH HAVE CHANGED, PLEASE INCLUDE A
 TRANSMITTAL LETTER INDICATING HOW EACH
 ITEM WAS ADDRESSED AND PROVIDE ONE COPY
 OF ALL OLD/VOIDED SHEETS FOR REFERENCE
 ONLY. NOTE: ONLY ONE CORRECTED DRAWING
 IN RED INK FOR REFERENCE FOR
 RESUBMITTAL.
  
 END OF COMMENTS:
  
 REVIEW BY MIKE PERSON
 (561) 805-6730
 FAX (561) 805-6731
 E-MAIL [email protected]
 UNDER SUPERVISION OF K.STEVENS
 (561) 805-6721