2007-03-12 14:12:49 | DENIED |
| REFERENCE: FBC-2004 PLUMBING; FBC-2004 CHAPTER 1, CITY |
| OF WEST PALM BEACH AMENDMENTS; |
| |
| THE FOLLOWING CORRECTIONS ARE REQUIRED FOR PLUMBING |
| PLAN REVIEW TO MEET CODE COMPLIANCE: |
| |
| 1. PER FBC-2004 CHAPTER 1, SECTION 106.1.1 INFORMATION |
| ON CONSTRUCTION |
| DOCUMENTS. CONSTRUCTION DOCUMENTS SHALL |
| BE OF SUFFICIENT CLARITY TO INDICATE THE |
| LOCATION, NATURE AND EXTENT OF THE WORK |
| PROPOSED AND SHOW IN DETAIL THAT IT WILL |
| CONFORM TO THE PROVISIONS OF THIS CODE |
| AND RELAVENT LAWS, ORDINANCES, RULES AND REGULATIONS, |
| AS DETERMINED BY THE |
| BUILDING OFFICIAL. |
| |
| 2. SHEET PG.2, SANITARY ISOMETRIC RISER DIAGRAM: PER |
| FBC-2004 CHAPTER 1, SECTION 106.3.5.4 RESIDENTIAL (ONE |
| AND TWO-FAMILY) PLEASE SUBMIT A PLUMBING SANITARY |
| ISOMETRIC RISER DIAGRAM INDICATING ALL WASTE, VENTS, |
| TRAPS AND SIZES WITH CLEANOUT LOCATIONS. |
| NOTE: THE SUBMITTED DRAWING IS NOT AN ISOMETRIC, IS NOT |
| CODE COMPLIANT, AND DOES NOT REFLECT THE FLOOR PLAN. |
| PLEASE REFERENCE THE ATTACHED CORRECTED SANITARY |
| ISOMETRIC RISER DIAGRAM TO THE PLUMBING COMMENTS FOR |
| THE RESUBMITTAL. |
| |
| 3. SHEET PG. 2, SANITARY ISOMETRIC RISER DIAGRAM: PER |
| FBC-2004 PLUMBING, SECTION 1002.1 A FIXTURE SHALL NOT |
| BE DOUBLE TRAPPED. A WATER CLOSET HAS AN INTEGRAL TRAP |
| AND A TRAP NEED NOT BE INDICATED. |
| |
| 4. SHEET PG. 2, SANITARY ISOMETRIC RISER DIAGRAM: PER |
| FBC-2004 PLUMBING, SECTION 1002.1 EACH PLUMBING FIXTURE |
| SHALL BE SEPERATELY TRAPPED BY A WATER SEAL TRAP. |
| NOTE: TRAP REQUIRED FOR TUB. |
| |
| 5. SHEET PG.2, SANITARY ISOMETRIC RISER DIAGRAM: |
| (A) 708.3.5 BUILDING DRAIN AND BUILDING |
| SEWER JUNCTION. THERE SHALL BE A |
| CLEANOUT NEAR THE JUNCTION OF THE |
| BUILDING DRAIN AND THE BUILDING SEWER. |
| NOTE: PLEASE INDICATE THS CLEANOUT AS A TWO-WAY |
| CLEANOUT. |
| |
| (B) 708.7 MINIMUM SIZE. CLEANOUTS SHALL |
| BE THE SAME NOMINAL SIZE AS THE PIPE |
| THEY SERVE UP TO 4 INCHES (102MM). |
| NOTE: FULL SIZE CLEANOUT (3") REQUIRED FOR WASHING |
| MACHINE. |
| |
| (C) 708.9 ACCESS. ACCESS SHALL BE |
| PROVIDED TO ALL CLEANOUTS. |
| NOTE: CLEANOUT FOR WASHING MACHINE SHALL BE LOCATED |
| FOUR FEET ABOVE FINNISH FLOOR (4' A.F.F.) |
| |
| 6. SHEET PG. 2, SANITARY ISOMETRIC RISER DIAGRAM: PER |
| FBC-2004 PLUMBING, SECTION 406.3 STANDPIPE REQUIRED FOR |
| WASHING MACHINE. PLEASE INDICATE ON THE RESUBMITTAL. |
| |
| ********IMPORTANT INFORMATION |
| IN ORDER TO EXPIDITE PLAN REVIEW: WHEN RESUBMITTING, |
| PLEASE REPLACE ONLY SHEETS |
| WHICH HAVE CHANGED, PLEASE INCLUDE A |
| TRANSMITTAL LETTER INDICATING HOW EACH |
| ITEM WAS ADDRESSED AND PROVIDE ONE COPY |
| OF ALL OLD/VOIDED SHEETS FOR REFERENCE |
| ONLY. NOTE: ONLY ONE CORRECTED DRAWING |
| IN RED INK FOR REFERENCE FOR |
| RESUBMITTAL. |
| |
| END OF COMMENTS: |
| |