2007-03-08 09:23:46 | |
| |
| DENIED/INCOMPLETE INFORMATION |
| |
| PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE |
| COMPLIANCE AND RESUBMIT FOR REVIEW. |
| |
| 1} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT |
| SIZE AND TYPE, GROUNDING DETAILS. 215.5 |
| |
| 2} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW |
| VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE |
| SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE |
| DISTINGUISHED FROM ALL OTHERS." |
| |
| 3} IF THE MAIN DISCONNECT IS NEW,OBTAIN THE |
| AVAILABLE FAULT CURRENT AT THE UTILITY |
| AND CALCULATE THE SAME AT THE EQUIPMENT. |
| INDICATE THE AIC RATING FOR THE |
| EQUIPMENT IS EQUAL TO OR GREATER THAN |
| THE AVAILABLE FAULT.PER 110.9 AND 110.10: |
| |
| 4} REGARDING NOTE #7: WHETHER OR NOT THE EXISTING |
| SERVICE CAN BE USED AS A TEMPORARY FOR CONSTRUCTION |
| WOULD BE AT THE DISCRETION OF THE ELECTRICAL INSPECTOR, |
| WHO WOULD MAKE THAT DETERMINATION AS A SAFETY ISSUE. |
| REGARDLESS, GFI PROTECTION PER 590.6. |
| |
| 5} 210.52(C)(3) PENINSULAR COUNTER SPACES AT LEAST ONE |
| RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH PENINSULAR |
| COUNTER SPACE WITH A LONG DIMENSION OF 600 MM (24 IN.) |
| OR GREATER AND A SHORT DIMENSION OF 300 MM (12 IN.) OR |
| GREATER. A PENINSULAR COUNTERTOP IS MEASURED FROM THE |
| CONNECTING EDGE. EXCEPTION TO (5): TO COMPLY WITH THE |
| CONDITIONS SPECIFIED IN (1) OR (2), RECEPTACLE OUTLETS |
| SHALL BE PERMITTED TO BE MOUNTED NOT MORE THAN 300 MM |
| (12 IN.) BELOW THE COUNTERTOP. RECEPTACLES MOUNTED |
| BELOW A COUNTERTOP IN ACCORDANCE WITH THIS EXCEPTION |
| SHALL NOT BE LOCATED WHERE THE COUNTERTOP EXTENDS MORE |
| THAN 150 MM (6 IN.) BEYOND ITS SUPPORT BASE. |
| |
| 6} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST |
| PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC. |
| |
| IF THERE ARE ANY QUESTIONS PLEASE CALL. |
| |