Plan Review Notes
Plan Review Notes For Permit 07020611
Permit Number 07020611
Review Stop E
Sequence Number 1
Notes
Date Text
2007-03-08 09:23:46 
  
 DENIED/INCOMPLETE INFORMATION
  
 PLEASE MAKE THE FOLLOWING CORRECTIONS FOR CODE
 COMPLIANCE AND RESUBMIT FOR REVIEW.
  
 1} PROVIDE A RISER DIAGRAM WITH CONDUCTOR AND CONDUIT
 SIZE AND TYPE, GROUNDING DETAILS. 215.5
  
 2} PROVIDE A PANEL SCHEDULE PER 408.4. PLEASE SEE NEW
 VERBAGE FOR 2005 NEC: "THE IDENTIFICATION SHALL INCLUDE
 SUFFICIENT DETAIL TO ALLOW EACH CIRCUIT TO BE
 DISTINGUISHED FROM ALL OTHERS."
  
 3} IF THE MAIN DISCONNECT IS NEW,OBTAIN THE
 AVAILABLE FAULT CURRENT AT THE UTILITY
 AND CALCULATE THE SAME AT THE EQUIPMENT.
 INDICATE THE AIC RATING FOR THE
 EQUIPMENT IS EQUAL TO OR GREATER THAN
 THE AVAILABLE FAULT.PER 110.9 AND 110.10:
  
 4} REGARDING NOTE #7: WHETHER OR NOT THE EXISTING
 SERVICE CAN BE USED AS A TEMPORARY FOR CONSTRUCTION
 WOULD BE AT THE DISCRETION OF THE ELECTRICAL INSPECTOR,
 WHO WOULD MAKE THAT DETERMINATION AS A SAFETY ISSUE.
 REGARDLESS, GFI PROTECTION PER 590.6.
  
 5} 210.52(C)(3) PENINSULAR COUNTER SPACES AT LEAST ONE
 RECEPTACLE OUTLET SHALL BE INSTALLED AT EACH PENINSULAR
 COUNTER SPACE WITH A LONG DIMENSION OF 600 MM (24 IN.)
 OR GREATER AND A SHORT DIMENSION OF 300 MM (12 IN.) OR
 GREATER. A PENINSULAR COUNTERTOP IS MEASURED FROM THE
 CONNECTING EDGE. EXCEPTION TO (5): TO COMPLY WITH THE
 CONDITIONS SPECIFIED IN (1) OR (2), RECEPTACLE OUTLETS
 SHALL BE PERMITTED TO BE MOUNTED NOT MORE THAN 300 MM
 (12 IN.) BELOW THE COUNTERTOP. RECEPTACLES MOUNTED
 BELOW A COUNTERTOP IN ACCORDANCE WITH THIS EXCEPTION
 SHALL NOT BE LOCATED WHERE THE COUNTERTOP EXTENDS MORE
 THAN 150 MM (6 IN.) BEYOND ITS SUPPORT BASE.
  
 6} THE PERSON TAKING RESPONSIBILITY FOR THE DESIGN MUST
 PRINT AND SIGN THEIR NAME TO SAME PER 106.3.4.3. FBC.
  
 IF THERE ARE ANY QUESTIONS PLEASE CALL.
  